5
2.2.2 Output Connections
Built in charge divider/isolator circuitry allows up to three separate battery banks (five banks optional) to be
connected to the charger. The charge divider uses one common negative connection for all batteries. The positive
cable from each battery should be connected to a separate positive DC output terminal. See Figure 3 and 4. Select
proper size for the DC wiring from the wire size Table 2 above. If the distance between the charger’s DC output
and the battery/load exceeds 10 feet, use the Power Cable Guide in
Appendix C
to minimize the voltage drop
across the wire distance.
Figure 3 – MSM Input and Output Terminals
CAUTION:
When connecting the DC cables to the battery, be certain the positive terminal of the charger
is connected to the positive battery terminal and the negative terminal is connected to the negative
battery terminal
Figure 4 - Typical MSM system configuration
Shown with Optional 5 Battery Charger Divider