INSTRUCTION/OPERATING AND TROUBLESHOOTING MANUAL FOR MODEL EC
Page 7 of 11
INSTALLERS INFORMATION
The table below lists the AC and the DC minimum wire size requirements. At distances exceeding
10 feet, the DC wire size should be chosen to keep the voltage difference between the unit's
terminals and the battery at less than 1/2 volt when the unit is fully loaded. If the distance
between the unit and the battery exceeds 10 feet, use the Power Cabling Formulas to determine
wire size.
WIRE SIZE TABLE
(Based upon unit fuse size)
WIRE SIZE EQUIPMENT
REQUIREMENT GROUNDING
FUSE CUSTOMER CONDUCTOR
SIZE CONNECTION MINIMUM
-------------------------------------------------------
1
#14
#14
3
#14
#14
4
#14
#14
5
#14
#14
6
#14
#14
10
#14
#14
15
#12
#12
20
#12
#12
25
#10
#12
30
#10
#10
35
# 8
#10
40
# 8
#10
45
# 8
#10
50
# 8
#10
60
# 6
#10
70
# 6
# 8
80
# 4
# 8
90
# 4
# 8
100
# 4
# 8
110
# 2
# 6
125
# 2
# 6
130
# 2
# 6
WIRE SIZE EQUIPMENT
REQUIREMENT GROUNDING
FUSE CUSTOMER CONDUCTOR
SIZE CONNECTION MINIMUM
-------------------------------------------------------
150
#1
#6
175
#1/0
#6
200
#2/0
#6
225
#2/0
#4
250
#4/0
#4
300
250-MCM
#4
350
350-MCM
#2
400
400-MCM
#2
450
500-MCM
#2
500
600-MCM
#2
600
900-MCM
#1
700
1500-MCM
1/0
800
2/500-MCM
1/0
1000
2/800-MCM
4/0
1200
2/1000-MCM
4/0
1600
2/2000-MCM
4/0
2000
250-MCM
2500
350-MCM
3000
400-MCM
4000
500-MCM
5000
700-MCM
6000
800-MCM
NOTE: These are recommended wire sizes. All National and Local Wiring Codes must be followed.