![La Marche AUPS-2K-A1-ABD1-24V150A Installation And Operation Manual Download Page 13](http://html1.mh-extra.com/html/la-marche/aups-2k-a1-abd1-24v150a/aups-2k-a1-abd1-24v150a_installation-and-operation-manual_3139665013.webp)
7
2.4
Making the DC Input/Battery Connections
Before making any of DC input connections, make sure you have read and fully understand the DC Connection
Procedure below. Ensure that the Battery breaker is set to the OFF position. Select proper size for the DC wiring
from Table 4. If the distance between the systems DC input and the battery exceeds 10 feet, use the Power
Cable Guide below to minimize the voltage drop across the wire distance.
Power Cabling Guide
Use the following formulas and table to determine proper wire size for minimal voltage drop.
Table of Conventions
CMA
= Cross section of wire in circular MIL area
A
= Ultimate drain in amperes
LF
= Conductor loop feet
MaxAmp = Maximum allowable amperes for given voltage drop
AVD
= Allowable voltage drop
K
= 11.1 for commercial (TW) copper wire (KS5482-01)
= 17.4 for aluminum (KS20189)
Calculating Wire Size Requirements
AVD
K
LF
A
CMA
Calculating Current Carrying Capacity of Wire
K
LF
AVD
CMA
MaxAmp
2.4.1 DC Input/Battery Connection Procedure
Run the battery wiring to terminals marked positive
(+)
and negative
(
–
)
on the terminal block
TB4
inside the
system.
CAUTION:
The AUPS has a Reverse Polarity LED indicator and will illuminate if the batteries are
connected in reverse polarity. Do not close/turn on ANY of the DC breakers or damage to the AUPS
will occur.
SIZE
(AWG)
AREA
CIR.MILS
SIZE
(MCM)
AREA
CIR.MILS
18
1620
250
250000
16
2580
300
300000
14
4110
350
350000
12
6530
400
400000
10
10380
500
500000
8
16510
600
600000
6
26240
700
700000
4
41740
750
750000
3
52620
800
800000
2
66360
900
900000
1
83690
1000
1000000
0
105600
1250
1250000
00
133100
1500
1500000
000
167800
1750
1750000
0000
211600
2000
2000000
Table 5 -
Wire Size/Area Table
Figure 4
–