INSTALLATION, OPERATING AND TROUBLESHOOTING INSTRUCTIONS FOR MODEL A75D / A75DE –

THREE PHASE

 

Page 13 of 20 

 

ELECTRICAL CONNECTIONS & FIELD WIRING 

A  terminal  board  is  provided  for  connecting  the  AC  input  and  DC  output.    A  ground  wire  must  be 
connected to the unit’s case ground.  

 

AC INPUT 

Make sure that AC power is off at the main AC breaker box before installation begins. 
 
Make  sure  that  the  input  source  is  the  same  voltage  and  frequency  as  that  which  is  marked  on  the 
nameplate of the rectifier. 
 
The  wire  size  and  distribution  protection  should  be  adequate  for  the  nameplate  input  current  of  the 
rectifier plus the overload current (usually 10%-15% higher than the nominal rating). 
 
An adequate earth ground lead should be connected to the terminal marked “GROUND” or “GND”. 

 

DC OUTPUT

 

Make  sure  that  the  battery  voltage,  which  is  being  connected  to  the  rectifier,  matches  the  rectifiers 
output voltage. 
 

*****OBSERVE PROPER POLARITY!***** 

 
The negative wire from the battery must be connected to the terminal marked “NEGATIVE” or “NEG” and 
the positive wire from the battery must be connected to the terminal marked “POSITIVE” or “POS” on the 
rectifier. 
 
To prevent the DC output breaker from tripping when connecting the battery, connections to the power 
supply and batteries should be done in the following order (single power supply). 
 

1.

 

Connect AC input line to the terminal block provided.  Be sure the AC circuit breaker is off. 

2.

 

Observe  the  polarity  of  the  battery  cables  and  the rectifier  output.    Connect  the  negative  battery  cable  to  the 
negative rectifier output terminal.  

3.

 

Energize  the  unit  by  turning  the  AC  breaker  to  the  “ON”  position.      This  will  charge  the  capacitors  inside  the 
power  supply and eliminate heavy arcing  when  the remaining battery cable is connected.  After approximately 
one (1) minute, turn off the power supply and immediately connect the remaining battery cable. 

4.

 

Connect the loads. 

5.

 

Turn  the  AC  breaker  to  the  “ON”  position  again  and  the  rectifier  will  commence  charging  the  batteries  and 
powering the load. 

LOAD SHARING 

A load sharing circuit is provided as a standard feature of the A75D/A75DE.  When connected two (2) or 
more identical A75D/A75DE units are forced to share the load equally (less than +/- 5%).  To load share, 
connect  the  unit  outputs  (must  be  the  same  DC  voltage)  in  parallel  and  connect  the  LS  terminals 
together.    If  the  charger  is  equipped  with  a  Remote  Equalize  Terminal,  connect  the  RE  terminals 
together.  The remote equalize connection forces the chargers to enter equalize mode at the same time. 
 

GROUND DETECTION 

If ground detection is desired, the green wire should be installed in the GND DET terminal of J9 terminal 
block of the S2A-362 control PCB.  To disable, move wire to GND DET DEFEAT terminal of J9. 
 
 
 

Summary of Contents for A75D

Page 1: ...Digital METERS THREE PHASE ECN DATE CPN124997 20535 8 14 20098 8 13 20084 8 13 19784 12 12 106 BRADROCK DRIVE DES PLAINES IL 60018 1967 847 299 1188 FAX 847 299 3061 ISSUE DATE ECN 19609 7 12 INSTRUCT...

Page 2: ...UTMOST IMPORTANCE THAT EACH TIME BEFORE USING THIS UNIT YOU READ THIS MANUAL AND FOLLOW THE INSTRUCTIONS EXACTLY To reduce risk of battery explosion follow these instructions and those published by t...

Page 3: ...Gases from the battery will corrode and damage equipment A sealed maintenance free or valve regulated lead acid VRLA may be placed below this equipment Never allow the battery electrolyte to drip on t...

Page 4: ...provide a copy of the claim to La Marche Mfg may void warranty service for any physical damages reported for repair HANDLING WARNING Equipment can be very heavy and top heavy Use adequate manpower or...

Page 5: ...f the battery cables charger output and relay rack terminals Connect the proper battery cable to the ground bar or battery charger output terminal Energize the power supply by turning on the units AC...

Page 6: ...75D A75DE series battery chargers provide separate voltage adjustments for floating or equalizing lead or nickel cadmium cells The float or equalize mode of operation is selected by pressing the equal...

Page 7: ...E PHASE VOLTAGE MODEL NUMBER D B C A75D A75DE 208 240 480 50 24V 30 26 13 75 24V 44 38 19 100 24V 59 51 26 125 24V 74 64 32 150 24V 89 77 38 200 24V 118 102 51 50 48V 15 13 6 75 48V 22 19 10 100 48V 3...

Page 8: ...E terminals of all chargers can be connected together to ensure all chargers automatically switch into and out of equalize mode together PROTECTION Current Walk In The output current gradually increas...

Page 9: ...terminals together If the charger is equipped with a Remote Equalize Terminal connect the RE terminals together CURRENT WALK IN Output current will gradually increase after the battery charger is tur...

Page 10: ...INFORMATION MINIMUM WIRE SIZES See Wire Size Chart lists the ac input and dc output minimum wire size requirements At distances exceeding 10 feet the dc wire size should be chosen to keep the voltage...

Page 11: ...500000 3 52620 400 400000 1750 1750000 2 66360 500 500000 2000 2000000 DENOTES ALL SIZES LARGER THAN 0000 ARE EXPRESSED IN MCM TABLE OF CONVENTIONS CMA Cross section of wire in circular MIL area A Ult...

Page 12: ...le lists the AC input and the DC output minimum wire size requirements At distances exceeding 10 feet the DC wire size should be chosen to keep the voltage difference between the units DC output termi...

Page 13: ...done in the following order single power supply 1 Connect AC input line to the terminal block provided Be sure the AC circuit breaker is off 2 Observe the polarity of the battery cables and the rectif...

Page 14: ...changing the rectifier current limit between 50 110 of rated output Turning the adjustment which is located on the unit front panel clockwise lowers the current limit turning counterclockwise raises...

Page 15: ...lashing LED Solid LED High DC voltage 2 45 Vpc Lead Acid High DC voltage shutdown HVSD 2 5 Vpc Lead Acid Low DC current 5 A Timer mode Mode 0 Equalize Time 8 Hours OPT 46R RELAY PACKAGE 2 SETS OF FORM...

Page 16: ...indicate The timer will automatically return the charger to the float mode when the equalize cycle is complete MODE 1 DISPLAY indicates P01 This mode of operation automatically starts an equalize cycl...

Page 17: ...can be caused by defective batteries and customer loads make sure batteries and loads are free from defects NOTE If the problem is found to be located in the printed circuit boards the board should be...

Page 18: ...output Meter should not indicate If the meter reads full scale deflection this indicates an ac dc short During shipping an AC wire may rub against the DC lugs terminals etc and cause a short These pro...

Page 19: ...nal components 4 Check front panel meters and alarms for accuracy 4th Year REPEAT ABOVE WITH THE ADDITION OF 1 Check relay contacts for pitting or corrosion 2 Check capacitors for leakage 7th Year REP...

Page 20: ...r installation installation adjustments and service arrangements Should minor adjustments be required the local La Marche sales representative should be contacted to provide this service only All sale...

Reviews: