background image

6)  Press ALARM key to confirm and press the MIN/MAX key to 

return the normal display mode or press the ALARM once more to 
toggle to another alarm setting mode. 

 

Wind direction alarm setting 

1)  Press the ALARM key to enter the normal time alarm 
2)  Continue to press the ALARM key until you reach the wind 

direction alarm set mode 

3)  Press and hold the SET key to enter the wind direction setting 

values. 

4)  Using the PLUS (+) or MINUS (-) keys select the desired wind 

direction and use the SET key to confirm or cancel each direction 
input 

5)  Press ALARM key to confirm and press the MIN/MAX key to 

return the normal display mode or press the ALARM once more to 
toggle to another alarm setting mode. 

 

Storm warning alarm setting 

Unlike the other weather alarms, the storm warning alarm is set by 
entering the main manual setting mode as follows: 
10) Press the SET key to enter the manual setting mode 
11) Continue to press the SET key until the Storm warning icon 

flashes (tendency arrow flashing downwards with the pressure 
values flashing) 

12) Set the desired inHg pressure value (9, 12, 15, 18, 21, 24, 27 

inHg) using the PLUS (+) or MINUS (-) keys 

13) Press the MIN/MAX key to confirm and return to the normal 

display. 

 

Storm warning alarm ON/OFF 

After storm warning alarm setting, the next mode to appear after 
pressing the SET key is the storm warning ON/OFF.  Use the PLUS 
(+) or MINUS (-) key to change the status to  AON or AOFF. Default 
setting is ON: 
 
Should the air pressure drop equal or below the pre-set inHg value 
within the last 6 hour period, then the downward tendency arrow will 
flash as an indication of possible storm. The base station will take 
hourly measurements as a point of reference.  The storm-warning 
indicator will stop flashing once the air pressure becomes more 
stable. 

 

Master Alarm – BUZZER OFF 

The time and all the weather alarms may have buzzer sound set to 
OFF by holding the MINUS (-) key down for about 3 seconds in 
normal display mode and the BUZZER OFF icon appears on the 
bottom left of the LCD.  When the BUZZER OFF is displayed, the 
time and all other weather alarms when activated will only flash but 
not sound regardless if that particular alarm has been set to the ON. 
To deactivate the BUZZER OFF, press the MINUS (-) key once more. 
 

General Alarm Icon 

The general alarm icon on the bottom right corner of the LCD will 
appear when any weather alarm is activated to show the user that a 
set weather condition has been reached. The activated alarm can be 
determined by checking the set alarm values against the MIN/MAX 
values reached. To deactivate the general weather alarm icon, press 
the ALARM key. 

 

Important 

When entering the alarm set mode for a specific weather or 
temperature condition, the corresponding alarm is automatically 
enabled (ON) when the SET key is pressed, regardless of its previous 
setting and the alarm value will flash to indicate that it has been 
activated.  Press the ALARM key to confirm the setting and continue 
pressing the ALARM key to toggle through each alarm mode until it 
returns to the normal display mode or press the MIN/MAX key at any 
time to exit the alarm setting modes. 

 

When a set weather alarm condition has been activated, that 
particular alarm will sound and flash for approximately 2 minutes but 
will continue to flash until weather conditions have become more 
steady. 

 

Weather Alarms 

The weather alarms are settable for when certain weather conditions 
are met according to the users requirements.  For example, the user 
can set the thresholds for the outdoor temperature to +86°F (high) 
and 14°F (low), while only enabling the high alarm and disabling the 
low alarm (i.e. temperatures <-14°F won’t trigger alarm, but 
temperatures >+86°F will). 

 

Alarm setting  

Minimum 

Maximum 

Storm threshold 

0.09 inHg 

0.27 inHg 

Summary of Contents for WS-2310

Page 1: ...10 Resetting factory settings 11 Function description 12 Operation keys 13 Basic programming modes 14 MIN MAX programming modes 15 Alarm programming modes 16 Auto memory for stored values 17 Accessor...

Page 2: ...wind and rain sensors are connected to the thermo hygro sensor for operating power and rely on it to communicate to the base station Weather data sent from the thermo hygro sensor can be done by wire...

Page 3: ...the data to the base station Operating power is taken from the thermo hygro sensor using a 32ft cable connection Features of Rain sensor The rain sensor measures the rainfall and sends the data to the...

Page 4: ...hree sockets for the wind sensor rain sensor and the base station 2 Connect the attached cables of wind and rain sensors to the corresponding sockets of the thermo hygro sensor by clicking them into p...

Page 5: ...ection for power back up in case of AC power failure A loss of power would desynchronize the base station and the sensor and no weather data will be received To Synchronize the units so that the weath...

Page 6: ...time intervals for the wind readings However the current wind speed or direction will be displayed once the time reading interval is reached For rainfall the interval readings may take up to 2 minute...

Page 7: ...ignals are received the system can be affixed Also if you have selected to use cable connection ensure that distances can reach all desired locations before affixing any unit permanently Once the wind...

Page 8: ...gro Sensor However if you wish to make a full reset of the base station and return to the original factory settings simultaneously press and hold the PRESSURE and WIND keys for about 5 seconds The bas...

Page 9: ...e displayed in different sections on the LCD If this is not the case please observe the notes on Interferences below Sunny Rainy Cloudy Notes to hPa sensitivity setting for weather forecasting The hPa...

Page 10: ...chill Outdoor dew point Rainfall 24h Rainfall 1h Rainfall total Notes to Dewpoint and Windchill Air can at a certain temperature only carry a certain amount of water water vapor which also increases a...

Page 11: ...current maximum minimum display modes Indoor temperature and humidity Outdoor temperature and humidity Outdoor wind chill Outdoor dew point Rainfall 24h 1h total WIND key To toggle between the followi...

Page 12: ...the manually set time and date and no further reception is attempted until the following day The manual setting takes the user through the following modes 1 8 level LCD contrast setting default level...

Page 13: ...Setting Alarms For alarm setting press the ALARM key once while in normal operation mode to enter the normal alarm time and by further pressing the ALARM key will toggle through each of the alarm mode...

Page 14: ...reach the indoor humidity high alarm set mode 3 Press and hold the SET key to enter the indoor humidity high setting values digits will start flashing and set the desired indoor humidity high by usin...

Page 15: ...time alarm 2 Continue to press the ALARM key until you reach the rain 1 hour alarm set mode 3 Press and hold the SET key to enter the rain setting values digits will start flashing and set the desire...

Page 16: ...Alarm BUZZER OFF The time and all the weather alarms may have buzzer sound set to OFF by holding the MINUS key down for about 3 seconds in normal display mode and the BUZZER OFF icon appears on the b...

Page 17: ...75 2 F with a pre set hysteresis of 1 8 F so that the alarm can be produced again Hysteresis values for the various weather data types are given in the following table For your convenience additional...

Page 18: ...the low battery indicator will light up on the LCD Please participate in the preservation of the environment by properly disposing of all used up batteries and accumulators at designated disposal poi...

Page 19: ...n the housing and screen of the base station only with a soft damp cloth Do not use abrasives or solvents Ensure that the rain sensor does not collect leaves or other dirt by checking the funnel for b...

Page 20: ...of 30 000 ft is around 8 85 inHg Resolution 0 01 inHg Relative humidity checking interval every 30 seconds Alarm duration 2 minutes approx Power consumption Base Station Batteries 3 x AA IEC LR6 1 5V...

Reviews: