background image

1. Read all safety precautions and follow L. B. White

recommendations when installing this heater.  If

during the installation or relocating of heater, you

suspect that a part is damaged or defective, call a

qualified service agency for repair or replacement.

2. Insure that all accessories that ship within the heater

have been removed from inside of heater and

installed.  This pertains to gas hose, regulators, etc.

3. Make sure the heater is properly positioned before

use.  Observe and obey all minimum safe distances of

the heater to the nearest combustible materials.

Minimum safe distances are given on the heater

dataplate and on page 4 of this manual.

4. The heater is designed for either indoor or outdoor

use.  For outdoor application, the heater is approved

for use with a .3 meter diameter by 4 meter long

flexible duct and air diffuser as supplied by the L.B.

White Co.  The heater shall not be used with any other

ducting or ductwork.

5. Heaters used in the vicinity of combustible tarpaulins,

canvas, plastic wind barriers, or similar coverings and

materials shall be located at least 3 m from the

coverings.  The coverings shall be securely fastened

to prevent ignition or upsetting of the heater due to

wind action on the covering or other materials.

6. The heater shall be located so that rain, ice, or snow

drainage from the structure does not affect heater

operation.  If the heater is installed outside, it must

be installed above any pooled or standing water.  If

the heater is located on the ground, a surrounding

trench is recommended to drain any rain, ice or snow

away from the heater.

7. The heater must be installed on a flat, horizontal

surface.

8. Locate the heater so as to protect it from tipover or

accidental movement.  

9. The heater must be installed so as not to interfere

with or obstruct normal exits, emergency exits, doors

and walkways.

10. Railing, fencing or suitable substitute materials

should be used as needed to isolate the heater from

people using and visiting the temporary structure.

11. Do not use the heater equipment area for storage of

any other materials.

12. The ground and surrounding terrain must be cleared

of any combustible vegetation and other combustible

materials.

13. Protect any electrical wiring and gas hoses with a

shield device of suitable nature to protect both from

equipment and people traffic.

14. This heater is supplied with a gas pressure regulator.

Make sure that gas regulator is appropriate for the

fuel source; LP-Gas or natural gas.  The regulator

must be properly connected to the LP-Gas cylinder or

natural gas supply to assure that gas pressure at the

inlet to the gas valve is regulated within the range

specified on the dataplate.  The heater’s gas

regulator (with pressure relief valve) should be

installed outside of the tent.  Any regulators within the

tent must be properly vented to the outside.  Local,

regional and national codes always apply to regulator

installation.  Contact your gas supplier or local L. B.

White agent if there are any questions.

15. Check all connections for gas leaks using approved

gas leak detectors.  Gas leak testing is performed as

follows:  Check all pipe connections, hose

connections, fittings and adapters upstream of the

gas control with approved gas leak detectors.  In the

event a gas leak is detected, check the components

involved for cleanliness and proper application of pipe

compound before further tightening.  Further tighten

the gas connections as necessary to stop the leak.

After all connections are checked and any leaks are

stopped, turn on the main burner.  Stand clear while

the main burner ignites to prevent injury caused from

hidden leaks that could cause flashback.  With the

Installation Instructions

GENERAL

WARNING

Fire  and  Explosion  Hazard

Can  cause  proper  damage,  severe  injury  or  death.

Disconnect power supply before wiring to prevent

electrical shock or equipment damage.

To avoid dangerous accumulation of fuel gas, turn off

gas supply at the appliance service valve before

starting installation, and perform gas leak test after

completion of installation.

8

WARNING

Fire  and  Explosion  Hazard

Do not use open flame (matches, torches, candles,

etc.) in checking for gas leaks.  

Use only approved leak detectors.  

Failure to follow this warning can lead to fires or

explosions.

Fires or explosions can lead to property damage,

personal injury or loss of life.

Summary of Contents for Premier TS080

Page 1: ...nts you may have call us at 608 783 5691 Owner s Manual and Instructions Circulating Tent Heaters W6636 L B White Rd Onalaska WI USA 608 783 5691 Fax 608 783 6115 ATTENTION ALL USERS This heater has been designed and developed specifically for use as a direct fired circulating heater for tent heating applications The heater has been evaluated by Advantica Certification Services and found to confor...

Page 2: ...injury or loss of life GENERAL HAZARD WARNING Failure to comply with the precautions and instructions provided with this heater can result in Death Serious bodily injury or burns Property damage or loss from fire or explosion Asphyxiation due to lack of adequate air supply or carbon monoxide poisoning Electrical shock Read this Owner s Manual before installing or using this product Only properly t...

Page 3: ...on The L B White Co Inc has a policy of continuous product improvement It reserves the right to change specifications and design without notice SECTION PAGE General Information 3 Heater Specifications 4 Fuel Information for Country of Destination 5 Safety Precautions 6 Installation Instructions General 8 Heater Sizing Guidelines 10 Cylinder Selection 10 Wheel Assembly Model TS170 11 Leg Assembly M...

Page 4: ...L P Natural L P Natural Gas Gas Gas Gas Model Ventilation Air Required 950 Cubic Meters 2 050 Cubic Meters to Support Combustion per Hour per Hour Burner Manifold Pressure Relative to Gas Category Electrical Supply Volts Hz Phase Amp Draw Dimensions L x W x H Minimum Safe Distances From Nearest Combustible Materials STARTING CONTINUOUS OPERATION Motor Characteristics Fuel Consumption Per Hour Inle...

Page 5: ...E 20 mbar L P Gas I3B P 30 mbar Nat Gas I2H 20 mbar L P Gas I3P 37 50 mbar Nat Gas I2E 20 25 mbar L P Gas I3P 30 50 mbar Nat Gas I2L 25 mbar 1 68 kg hr 3 55 kg hr 2 34 m3 hr 4 74 m3 hr 1 68 kg hr 3 55 kg hr 2 34 m3 hr 4 74 m3 hr propane 1 68 kg hr 3 55 kg hr butane 1 71 kg hr 3 62 kg hr 2 34 m3 hr 4 74 m3 hr 1 68 kg hr 3 55 kg hr G 20 2 34 m3 hr 4 74 m3 hr G 25 2 6 m3 hr 5 51 m3 hr 1 68 kg hr 3 55...

Page 6: ... poisoning in humans leading to serious injury or death Symptoms of carbon monoxide poisoning can include headaches dizziness and difficulty in breathing Asphyxiation Hazard Some people cannot smell well Some people cannot smell the odor of the man made chemical added to propane LP or natural gas You must determine if you can smell the odorant in these fuel gases Learn to recognize the odor of pro...

Page 7: ... the heater Doing so may cause improper combustion or damage to heater components leading to property damage 9 The hose assembly shall be visually inspected prior to each use of the heater If it is evident there is excessive abrasion or wear or if the hose is cut it must be replaced prior to the heater being put into operation The hose assembly shall be protected from traffic building materials an...

Page 8: ...ials 12 The ground and surrounding terrain must be cleared of any combustible vegetation and other combustible materials 13 Protect any electrical wiring and gas hoses with a shield device of suitable nature to protect both from equipment and people traffic 14 This heater is supplied with a gas pressure regulator Make sure that gas regulator is appropriate for the fuel source LP Gas or natural gas...

Page 9: ... according to instructions on heater or within owner s manual 18 This heater can be configured for use with either L P gas vapor withdrawal or natural gas Consult the dataplate located on the exterior of the burner end door for the gas type of the specific heater Do not use the heater in an L P gas liquid withdrawal system or application If you are in doubt contact your local agent or the L B Whit...

Page 10: ...able of supplying the vapor necessary to feed the heater Looking at 0º C scale you can see that a 47 KG cylinder is only capable of supplying the full heat load for one hour REMINDER The minimum cylinder size shall be 47 KG The minimum number of 47 KG cylinders used shall be TS080 1 TS170 2 The maximum number of cylinders used within the area to be heated shall be three 47 KG Have your LP gas supp...

Page 11: ... it is securely attached 7 Snap hub caps into wheel slots FIG 1 1 Placing cardboard or other material under the hinged burner access panel to prevent scratching tip the heater back so the louvered air inlet panel is facing up 2 Mount the support leg to the underside of the base using four 12 7 mm bolts and lock washers provided FIG 2 WHEEL ASSEMBLY MODEL TS170 LEG ASSEMBLY MODEL TS170 Mount the ho...

Page 12: ...read compound suitable for use with L P gas or natural gas on the threaded connections 2 Assemble the components together as shown Tighten securely 3 The hose and regulator should be stored on the heater when the heater is not being used FIG 5 HOSE AND REGULATOR ASSEMBLY Optional Accessory HEATER CASE SIDE MOUNTING HOLES SCREW REGULATOR MOUNTING BRACKET MODELTS170 ONLY HOSE ADAPTER HOSE GASVALVE I...

Page 13: ...IREMENTS SLOTS DUCT ADAPTER TABS DUCT KIT 1 Mount the duct to the heater by inserting the tabs on the duct adapter into the vertical slots on each side of the blower outlet 2 Push down on the duct adapter to secure the adapter in place to the heater 3 Extend the duct out to its full 3 6 meter length 4 The tent material may then be draped around the duct outlet or an optional air diffuser part numb...

Page 14: ...rner end of the heater for assistance in troubleshooting or refer to the troubleshooting guide within this Owner s Manual Only qualified and properly trained personnel shall service or repair the heater 6 On a call for heat the motor will start up and run for five 5 seconds prior to ignition trial This pre purge is a safety feature and a normal operational characteristic After five 5 seconds the i...

Page 15: ...heater can cause severe personal injury or property damage due to water and or cleaning solution In electrical components connections and wires causing electrical shock or component failure On gas control valves causing corrosion which can result in gas leaks and fire or explosion from the leak This heater must be cleaning in accordance with the manufacturer s instructions without being subjected ...

Page 16: ...rew s of the fan are on the flats of motor shaft when tightening FIG 9 MOTOR AND FAN WHEEL ASSEMBLY 1 Shut off the gas supply to the heater 2 Disconnect the heater from its electrical supply 3 Open the louvered access panel on the motor end of the heater 4 Remove the two 2 sheet metal screws holding the switch with bracket to blower housing Remove the air proving switch assembly by turning the swi...

Page 17: ...acceptable inlet pressures to the gas control valve are shown in the heater specifications table and also on the heater s dataplate The inlet pressure may need adjustment as necessary to achieve proper outlet pressure Inlet pressure is checked in the same manner as outlet pressure h After pressures have been checked shut off the gas supply and electrical supply to the heater remove the gauge and t...

Page 18: ...SET HIGH LIMIT SWITCHES WARNING Fire Hazard Do not operate the appliance with the high limit switches bypassed Operating the heater with bypassed high limit switches may lead to overheating possibly resulting in a fire with subsequent damage to the heater building damage or loss of livestock IGNITER IGNITER CABLE IGNITER SENSOR MOUNTING BRACKET SCREWS IGNITERTOPTO BURNERTOP 12 7 MM BURNER PORT ELE...

Page 19: ... selector switch is positioned to Vent Ignition Control Lock Out For safety the ignition control in this heater continually monitors air proving components fan motor and air proving switch and burner flame The ignition control will lock out the control system if it does not recognize burner flame presence or if air proving components fail Either condition causes control valve closure to occur Othe...

Page 20: ...ll for Heat Occurs from the Thermostat Thermostat Sends Line Voltage to the Transformer and to the Motor Relay Contacts Transformer Sends 24 Volts to the Circuit Breaker Circuit Breaker Sends 24 Volts to the Ignition Control Module Red L E D on Control Module is Illuminated Ignition Control Module Performs Self Safety Check Internal Components are Tested Air Proving Circuit is Checked Ignition Con...

Page 21: ...Ignition Control Module LED is Steady On No Flash Pattern Ignition Control Lock Out Due to A Ignition Control Module Failure B Poor Electrical Quality Frequency Line Noise Line Spikes Reset Ignition Control Module A If Control Module Does Not Reset Replace Ignition Control Module B Have Qualified Electrician Check the Power Supply HEATING MODE ...

Page 22: ... Supply Check Circuit Breakers in Building Electrical System Check Power Cord for Continuity Replace Thermostat Replace Selector Switch Are 24 Volts Supplied from Transformer Replace Transformer No No No No No No Yes Is Circuit Breaker Receiving 24 Volts Check Wiring Repair as Necessary Replace Ignition Control Module Yes Is Proper Voltage Supplied to Transformer Check Electrical Connections and P...

Page 23: ...ng and centered over burner slot If High Limit Switches are Tripped Reset the Switch es and Determine Cause of High Limit Tripping See Important Notes on page 25 Remove Burner Orifice and Clean Hole with a Soft Brush or Compressed Air Replace Orifice if Necessary Check Igniter Gap and Regap if Necessary to 3 mm Provide Proper Gas Supply and Pressure to Heater Refer to Dataplate Is 24 Volts Supplie...

Page 24: ...ctrical Connections to Motor Relay Repair or Replace as Necessary Check Wiring Between Control Module and Motor Relay Repair as Necessary If Wiring is Good Replace Ignition control Module Replace Motor Relay No Is Fan Wheel Loose On Motor Shaft No Is Proper Voltage Supplied to Fan Motor No No Is Air Proving Switch Stuck Open or Shorted Perform Continuity Check Is Ignition Control Module Sending 24...

Page 25: ... NOT leave the jumper wire on and operate if part is defective Replace component IMMEDIATELY or do not operate unit 3 The ignition control module sends and receives voltages throughout the entire operation sequence The ignition control module terminals should also be checked for delivering proper voltages in addition to the individual components as indicated by the respective flash pattern to make...

Page 26: ...nections Verify Proper Voltage with a Voltage Tester Contact a Qualified electrician if Proper voltage is not Present No No Yes Is Proper Voltage Supplied to Selector Switch from Power Cord No Problem Motor Hums Does Not Run Is Fan Binding on Housing Check for Damage to Motor and Fan Assembly and Housing Repair or Replace as Necessary Yes Reconnect Wires to Capacitor Defective Capacitor Replace th...

Page 27: ...BLUE BLUE WHITE GREEN YELLOW GREEN YELLOW YELLOW THERMOSTAT GROUND BROWN BROWN BROWN BROWN BROWN BLUE BLUE BLUE BLUE BLUE GREEN YELLOW BLUE BLUE BLUE WHITE WHITE WHITE WHITE HEAT OFF VENT N N N POWER CORD TERMINAL STRIP CIRCUIT BREAKER BLUE BROWN BROWN BROWN BLUE BLUE WHITE WHITE GRAY GRAY GRAY RED RELAY WHITE GRAY RED ORANGE ORANGE YELLOW GREEN YELLOW AIR PROVING SWITCH L E D INDICATOR MANUAL RES...

Page 28: ...el gas in the event burner flame goes out Gas Hose Flexible connector used to deliver gas from supply line in building to heater Heat Chamber Metal fire box within the appliance that provides an area where burner flame mixes with combustion air thereby providing heat High Limit Switch Safety device wired into the control system which is used to break an electrical circuit to the gas control valve ...

Page 29: ...Parts Identification 29 PARTS SCHEMATIC TS080 47 46 43 42 45 44 33 41 40 39 31 30 29 27 26 25 23 22 21 19 12 11 10 18 17 16 7 9 8 6 5 15 14 13 24 28 4 32 34 35 36 37 38 3 2B 2A 2 1 ...

Page 30: ... Gas Control L P Gas 21472 Valve Gas Control Natural Gas 21473 21 Wire Ignition Cable 09348 22 Igniter Sensor 06479 23 Bracket Igniter Sensor Mount 08906 24 Bracket Support Burner Casting 08933 25 Casting Burner 08921 26 Bracket Burner Flame Arrestor 08942 27 Spacer 02687 28 Bracket Casting Locator 07443 29 Bracket Limit Switch Wires 09767 30 Switch High Limit Heat Chamber 03933 31 Heat Chamber As...

Page 31: ...PARTS SCHEMATIC TS170 31 47 46 48 45 33 44 43 42 41 40 39 30 29 28 27 26 25 23 24 17 21 22 20 16 19 18 10 14 9 8 7 6 5 4 15 13 12 31 32 34 35 36 37 38 3 1 2 2A 2B ...

Page 32: ...Terminal Block 21150 21 Circuit Breaker 2 0 Amps 24 Volts 21080 22 Relay Motor 09819 23 Transformer 240 24 Volt 20659 24 Wire Ignition Cable 09348 25 Bracket Igniter Sensor Mount 09783 26 Igniter Sensor 06479 27 Casting Burner 03453 28 Spacer Burner 02687 29 Bracket Burner Mount 20029 30 Switch High Limit Heat Chamber 03933 31 Heat Chamber Assembly 09133 32 Fan Housing Assembly w Airflow Switch an...

Page 33: ...ellow 129 5 cm 21124 Wire Harness Ignition Control Module 21139 Wire Transformer to Terminal Block White 20 cm 21245 Wire Circuit Breaker to Transformer Gray 15 cm 21246 LABEL IDENTIFICATION Part Number TS080 TS170 Description Location L P Gas Natural Gas L P Gas Natural Gas Label Wiring Diagram Interior Door Burner End 21122 Label Troubleshooting Label Interior Door Burner End 21123 Nameplate Ext...

Page 34: ...defect occurs more than 12 months later than the date code but within 12 months from the date of purchase by the end user a copy of a bill of sale will be required to establish warranty qualification The warranty set forth above is the exclusive warranty provided by L B White and all other warranties including any implied warranties or merchantability or fitness for a particular purpose are expres...

Page 35: ...ve 89 336 EEC Electro Magnetic Compatibility Basis of Conformity Gas Appliance Directive by Type Examination Product Identification No 87AT62 Certificate No BG EC 87 98 62 Applied Standard prEN1596 May 1997 Manufacturing Surveillance BG plc Notified Body 0087 Certificate ECS 00153a Low Voltage Directive by Examination BG plc Notified Body 0087 Certificate BG TC 98 39 Applied Standard EN60335 1 199...

Reviews: