background image

1.

Read all safety precautions and follow L. B. White
recommendations when installing this heater.  If
during the installation or relocating of heater, you
suspect that a part is damaged or defective, call a
qualified service agency for repair or replacement.

2.

Make sure the heater is properly positioned before use
and is hung level.  Observe and obey all minimum safe
distances of the heater to the nearest combustible
materials.  Minimum safe distances are given on the
heater nameplate and on page 4 of this manual.

3.

For heaters intended for outdoor installation, the
heater is to be installed at least 18 inches above the
ground or to a height that would prevent snow
blockage of heater’s air inlet.

4.

The heater may be used either indoors or outdoors.
When the heater is mounted outdoors, use only the
ductwork supplied in the outdoor mounting kit.

5. The heater must have the proper gas regulator installed

for the application.  A regulator must be connected to
the gas supply so that gas pressure at the inlet to the
gas valve is regulated within the range specified on the
dataplate at all times.  Contact your gas supplier, or the
L.B. White Co., Inc. if you have any questions.

6.

The heater’s gas regulator (with pressure relief valve)
s h o u l d   b e   i n s t a l l e d   o u t s i d e   o f   b u i l d i n g .     A ny
regulators inside the buildings must be properly
vented to the outside.  Local, state and national
codes always apply to regulator installation.  Natural
gas regulators with vent limiting device may be
mounted indoors without venting to outdoors.

7.

All gas pressure regulators must be installed in strict
accordance with the manufacturer’s safety instructions.
These instructions accompany each regulator.

8.

Insure that all accessories that ship within the heater
have been removed from inside of heater and
installed.  This per tains to air diver ters, hose,
regulators, etc.

9.

Make certain that a sediment trap is installed at the
gas valve inlet to prevent foreign materials (pipe
compound, pipe chips and scale) from entering the
gas valve.  Debris blown into the gas valve may cause
that valve to malfunction resulting in a serious gas
leak that could result in a possible fire or explosion
causing loss of products, building or even life.  A
properly installed sediment trap will keep foreign
materials from entering the gas valve and protect the
safe functioning of that important safety component.  

10.

Any heater connected to a piping system must have
an accessible, approved manual shut of f valve
installed within six feet (6 ft.) of the appliance it
serves.  

11.

Check all connections for gas leaks using approved
gas leak detectors.  Gas leak testing is performed as
follows:  

-- Check all pipe connections, hose connections,

fittings and adapters upstream of the gas
control with approved gas leak detectors.  

-- In the event a gas leak is detected, check the

components involved for cleanliness and
proper application of pipe compound before
further tightening.  

-- Furthermore tighten the gas connections as

necessary to stop the leak.  

-- After all connections are checked and any

leaks are stopped, turn on the main burner.  

-- Stand clear while the main burner ignites to

prevent injury caused from hidden leaks that
could cause flashback.  

-- With the main burner in operation, check all

connections, hose connections, fittings and
joints as well as the gas control valve inlet and
outlet connections with approved gas leak
detectors.  

-- If a leak is detected, check the components

involved for cleanliness in the thread areas
and proper application of pipe compound
before further tightening.  

-- Tighten the gas connection as necessary to

stop the leak.  

-- If necessary, replace the parts or components

involved if the leak cannot be stopped.

-- Ensure all gas leaks have been identified and

repaired before proceeding.

WARNING

Fire or explosion hazard.

Can cause property damage, severe injury or death.

1. Disconnect power supply before wiring to prevent

electrical shock or equipment damage.

2. To avoid dangerous accumulation of fuel gas, turn 

off gas supply at the appliance service valve before
starting installation, and perform gas leak test after
completion of installation.

3. Do not force the gas control knob.  Use only your

hand to turn the gas control knob.  Never use any
tools.  If the knob will not operate by hand, the
control should be replaced by a qualified service
technician.  Force or attempted repair may result in
fire or explosion.

8

Installation Instructions

GENERAL

WARNING

Fire and Explosion Hazard

Do not use open flame (matches, torches, candles,
etc.) in checking for gas leaks.  

Use only approved leak detectors.  

Failure to follow this warning can lead to fires or
explosions.

Fires or explosions can lead to property damage,
personal injury or loss of life.

Summary of Contents for GUARDIAN Smart Sense AD250

Page 1: ...ding Heaters with Smart Sense Automatic Variable Rate Heat For Use with SmartBox Controller ATTENTION ALL USERS This heater has been designed tested and evaluated by L B White Co Inc as a direct gas f...

Page 2: ...line solvents paint thinner dust particles or unknown chemicals Failure to follow these instructions may result in a fire or explosion Fire or explosions can lead to property damage personal injury or...

Page 3: ...B White distributor dealer or the L B White Company Contact your local L B White distributor or the L B White Co Inc for assistance or if you have any questions about the use of the equipment or its...

Page 4: ...ed to Support Combustion CFM Burner Manifold Pressure in W C Net Weight lbs Shipping Weight lbs Electrical Supply Volts Hz Phase Amp Draw Starting Amps Includes Igniter Dimensions Inches L x W x H Min...

Page 5: ...environment controller is required for further operation See Fig 1 for a typical system diagram Each SmartBox controls two zones of heat two heaters er zone One sensor may be used for each zone of he...

Page 6: ...ht the appliance for you WARNING Do not use this heater for heating human living quarters Do not use in unventilated areas The flow of combustion and ventilation air must not be obstructed Proper vent...

Page 7: ...ving switch Never operate this heater with any safety device that has been bypassed Do not operate this heater unless all of these features are fully functioning 6 Do not operate the heater with its d...

Page 8: ...eep foreign materials from entering the gas valve and protect the safe functioning of that important safety component 10 Any heater connected to a piping system must have an accessible approved manual...

Page 9: ...fects found in performing any of the service or maintenance procedures must be eliminated and defective parts replaced immediately The heater must be retested by properly qualified service personnel b...

Page 10: ...TIONS SEDIMENT TRAP ASSEMBLY NIPPLE HOSE ADAPTER TEE NIPPLE CAP TO GAS CONTROL VALVE INLET EYEBOLT NUT FLATWASHER CAGE NUT CHAIN CASETOP NOTE REGULATORS SHOULD ALWAYS BE MOUNTED OUTDOORS IF CIRCUMSTAN...

Page 11: ...suitable for use with L P gas or natural gas on the threaded connections 2 Assemble the components together according to the figure This view is to show general assembly of the components only The reg...

Page 12: ...1 and 2 FIG 7 B Wiring from SmartBox to the heater s Smart Sense variable rate gas control valve a Connect Smart Sense gas control valve wiring for Zones 1 and 2 at SmartBox leads as shown in Fig 8 F...

Page 13: ...onnel shall service or repair the heater 5 On a call for heat the motor will start up and run for five 5 seconds This pre purge is a safety feature and a normal operational characteristic prior to ign...

Page 14: ...ee of dust c When washing with water observe and obey the Warning within these Cleaning Instructions This same Warning is also supplied on the heater 14 Cleaning Instructions Maintenance Instructions...

Page 15: ...and must be replaced Do not operate the heater with the switch jumpered Replace the part immediately An alternate method for checking the components is to perform a continuity check 5 Do not jumper t...

Page 16: ...off briskly rub the sensor rod with emery cloth or steel wool to remove any build up Restart the heater Ensure the igniter gap is 1 8 3 16 in and the igniter tip is positioned over the burner port ac...

Page 17: ...bout a minute before firmly pressing the reset button on the switch 6 Check for electrical continuity across the switch terminals to make sure the contacts have closed 7 Reinstall the switch back into...

Page 18: ...2 Do the readings at the inlet and outlet pressure gauges agree with that specified on the dataplate If so then no further checking or adjustment is required Proceed to section D 3 If the inlet press...

Page 19: ...s is essential as it will relate directly to problem solving provided by the flow charts The ignition control module is self diagnostic The red light on the module will flash a specific pattern depend...

Page 20: ...control terminal PS2 Ignition control powers the igniter and igniter sparks Ignition control sends 24 volts from terminal MV to gas control through high limit switch Ignition occurs Igniter continues...

Page 21: ...ive Replace ignition module Is proper voltage supplied to transformer Check electrical connections and power supply to transformer Repair as necessary No Yes 21 Heater does not cycle above minimum hea...

Page 22: ...seconds off repetitively for 15 minutes Heater has attempted three ignition trials Heater is in a 15 minute wait period before attempting three more trials for ignition If ignition is not achieved aft...

Page 23: ...efective motor or capacitor Replace motor Yes Remove obstruction Clean as necessary No Is fan wheel plugged with dirt No Is there an obstruction in blower outlet preventing air proving switch closure...

Page 24: ...o heater and check with a gauge No Remove orifice and burner casting Blow out with compressed air or clean with a soft brush No No No No No Is flame sensor insulator cracked No Is flame sensor properl...

Page 25: ...blems in three time flash pattern 1 The ignition control sends and receives voltages throughout the entire operation sequence The ignition control s terminals should also be checked for delivering pro...

Page 26: ...ROUND POWER CORD WHITE FAN MOTOR GAS CONTROLVALVE L1 IND L E D MV PS2 PS1 W FS R X C COM GREEN YELLOW BLACK DSI CONTROL TRANSFORMER IGNITER FLAME SENSOR HIGH LIMIT SWITCH AIR PROVING SWITCH BLACK BLAC...

Page 27: ...ical circuit to the gas control valve in event of overheat situation Ignition Control Module Controls the ignition sequence and operation of the heater as well as monitoring the safety sevices A major...

Page 28: ...28 Parts Identification PARTS SCHEMATIC 29 27 14 15 16 17 19 18 20 21 22 23 24 25 26 13 12 11 10 9 8 28 7 6 5 4 3 2 1...

Page 29: ...Orifice burner Propane Gas 570053 Natural Gas 572876 10 Burner 570655 11 Burner mounting hardware 570211 12 Igniter and sensor assembly 22473 13 High limit switch 505566 14 Heat chamber 570200 15 Case...

Page 30: ...urchase by the end user Warranty is automatic if a component is found defective within 12 months of the date code marked on the part If the defect occurs more than 12 months later than the date code b...

Page 31: ......

Reviews: