Owner’s Manual • Foreman

A. Heating Mode Operation

When the selector switch is positioned to heat and 

the thermostat is calling for heat, a set of green 

lights will illuminate (power ON and thermostat 

ON). The burner fan motor will pre purge for 45 

seconds. After the burner fan has pre purged, the 

igniter will spark and ignition will occur. The main 

blower has a time delay of 30 seconds before 

operation. The thermostat will cycle the heater ON 

or OFF based upon temperature setting.  The high 

limit LED will flash during pre/post purge cycle.

Note: 

  When the thermostat cycles the heater off 

or selector switch is switched to OFF, the 

main fan motor will continue to run for an 

additional 3 minutes to cool down the heat 

exchanger.

B. Vent Mode Operation

When the selector switch is positioned to vent, only 

the fan motor light will illuminate. The fan motor will

start, but the burner motor will not, nor will ignition 

occur. This feature is used typically when heat 

is not needed, but air circulation is required. The 

heater will not cycle on its thermostat setting. 

To discontinue the ventilation feature, position 

the switch to midpoint O or heat If you desire to 

use the ventilation feature, the fuel source is not 

needed. 

C. Off O

 

Position the switch to midpoint O

Safety Lock-Out

This heater is equipped with the Beckett GeniSys 

Advanced Burner Control. The GeniSys is used 

with a suitable cad cell flame sensor to control the 

oil burner motor, igniter, and oil solenoid valve.

■  The GeniSys Burner  controller has one ignition 

trial. If ignition is not achieved, the GeniSys 

burner control will enter a “soft lock-out” mode.

Soft lockout – the control has shut down for one of 

the following safety reasons:

a) The trial for ignition fail.

b) The cad cell did not detect flame.

c) Flame is lost during ignition trial.

d) Burner control will retry ignition in 60 seconds.

TO RESET THE CONTROL BOX 

Push the reset button on the GeniSys controller for 

1-second and verify the red light in the reset button 

shut off.

DIAGNOSTICS MODE

Status lights

Light Color

Solid

Flashing

Red

Hard lockout (1)

Soft lockout (2)

Green

Normal operation

Recycle (3)

Yellow

Pump prime mode (4) 

or reset button held 

for 15+ seconds

N/A

(1)  Recurrence of a soft lockout- to reset, push and hold the 

reset button for 15 seconds until the yellow light turns on.

(2)  Ignition failure, cad cell did not detect flame, or flame lost- 

to reset, push and release the reset button.

(3)  Control has entered a 60 second delay, and will repeat the 

ignition sequence.

(4) Purging air out of the fuel line.

The controller will only provide the diagnostics when 

the selector switch is set to HEAT 

■  It is normal for air to be trapped in the fuel line on 

new installations. The heater may require several 

trials for ignition before air is finally purged from line 

and ignition takes place.

Summary of Contents for Foreman

Page 1: ...vneR to view maintenance videos for L B White heaters WORLD PROVIDER INNOVATIVE HEATING SOLUTIONS 411 Mason Street Onalaska WI 54650 800 345 7200 608 783 5691 608 783 6115 fax www lbwhite com Foreman Ductable Indirect Fired Oil Heater CI230 230 000 Btuh 67 4 kW 1 2 Fuel Oil Owner s Manual and Instructions View this manual online at www lbwhite com Requires an app like QR Droid for Android or for i...

Page 2: ... amp CI500 CI750 20 amp 4 Set thermostat to desired room temperature or set thermostat selector switch to the manual position 5 This heater has a rocker style selector switch located on the side of the heater This switch allows for either heat mode or ventilate mode no heat 6 When the switch is set to heat three status lights will be activated in sequence as specific circuits are checked by the he...

Page 3: ... Out This heater is equipped with the Beckett GeniSys Advanced Burner Control The GeniSys is used with a suitable cad cell flame sensor to control the oil burner motor igniter and oil solenoid valve The GeniSys Burner controller has one ignition trial If ignition is not achieved the GeniSys burner control will enter a soft lock out mode Soft lockout the control has shut down for one of the followi...

Page 4: ...move the fan wheel assembly and brush or blow off and dust that may have accumulated on the fin Additionally make sure the burner air inlet is free of dust accumulation Clean all components of the heater with pressurized air a dry brush or a dry cloth Maintenance Instructions BEFORE EACH USE Check the area surrounding the heater to ensure it is clear and free of combustible materials gasoline and ...

Reviews: