Foreman Ductable Oil Indirect-Fired Heater
Owner’s Manual • Foreman
Start-Up Instructions
For initial start-up after heater installation, follow steps
1-5. For normal start-up, set the thermostat above room
temperature or set thermostat selector switch to the
manual position.
1. Follow all ventilation and safety information.
2. Fill tank with fuel.
3. This heater is wired with a ground connection for
your protection against electrical shock hazard. The
heater must be connected directly to a properly wired
and grounded electrical supply. Minimum breaker
size: CI230-15 amp, CI500/CI750-20 amp.
4. Set thermostat to desired room temperature or set
thermostat selector switch to the manual position.
5. This heater has a rocker style selector switch
located on the side of the heater. This switch
allows for either heat mode or ventilate mode
(no heat).
6. When the switch is set to heat , three status
lights will be activated in sequence as specific circuits
are checked by the heater controller. If the heater
does not light, and a status light is off, refer to the
trouble shooting section of this manual.
7. Do not exceed input rating stamped on nameplate
or manufacturer’s recommended pump pressure for
nozzle used. Make certain that the primary air supply
to main burner is open and free of dust, dirt and
debris for complete, proper combustion.