27
Superheat Calculations
+ 33 F Suction Temperature
Suction Pressure
66.7 PSIG
Example: R404
+ 33 F Suction temperature
28 F Suction pressure converted to temperature
= +5 F Superheat
Operation
Loading
Merchandise should not be placed in the fixture until all controls have been adjusted and the case is at the
proper temperature.
NOTE: AT NO TIME SHOULD THE CASE BE STOCKED BEYOND THE LOAD LINE
OR OVER THE FRONT EDGE OF ADJUSTABLE SHELVES.
All cases have load limit line markings. Product must be
kept within the load limit line for cases to function properly.