background image

(3) Make sure that all of the three lamps for phase check are on. 

If so, there is no open phase. When any of the three lamps is
Not on there is open phase.

Open phase check

Open phase on terminal 

Lamp "L1" is not on

where Red alligator clip 
is connected.

Open phase check

Open phase on terminal 

Lamp "L2" is not on

where Yellow alligator clip 
is connected.

Open phase check

Open phase on terminal 

Lamp "L3" is not on

where Blue alligator clip 
is connected.

*When  the  open  phase  check  lamps  are  not  on  the  rotating  disc

does not turn.

(4) Check  the  rotating  direction  of  the  inside  disc  through  the

phase sequence indication window.

*When  the  rotating  disc  turns  counter-clockwise  alternate  the

connection  of  the  two  of  the  three  alligator  clips.  Then,  the
rotating disc will turn clockwise.

*When  the  rotating  disc  turns  clockwise  phase  sequence  is

L1,L2 and L3 in order of the power source terminals where the
Red, Yellow and Blue alligator clips are connected.

Please Note

: New  European  harmonized  phase  colours  are

as follows.

Red = Brown

Protective Earth = Green yellow

Yellow = Black

Neutral = Blue

Blue = Grey

DISTRIBUTOR

Kewtech Corporation Limited

St Catherine s Grove, Lincoln, LN5 8NA England
Phone : 01522 546888
Fax 

: 01522 531788

URL : www.kewtechcorp.com
E-mail : [email protected]

92-1739

12-04

Printed in Japan

●Functional Design

Small, Lightweight and portable. Designed for maximum ease of
operation and ruggedness.

●Safety Design

No  exposed  metal  parts.  Safety  features  are  incorporated
including the instant push button switch operation.

SPECIFICATIONS

Standard 

: IEC 61010-1 CAT.

600V Pollution degree 2

Voltage

: 110V to 600V

Frequency 

: 50Hz / 60Hz

Withstand Voltage : 5,550V AC for one minute
Time Limit for Continuous Use : Within  5  minutes  in  case  voltage

is above 500V.

Dimensions

: 106 (L) x 75 (W) x 40 (D) mm

Weight

: Approx. 350g

Cord

: 1.2m each of Red (L1), Yellow (L2) and Blue

(L3) cord

Fuse

: 0.5A / 600V (F)

Accessories

: Instruction Manual, Carrying Case

OPERATING INSTRUCTIONS

(1) Connect  colour  coded  alligator  clips  or  prods  to  the  terminals

of a 3-phase power source where a rotating electrical machine
such as a motor will be connected or input to a building.

(2) Press the push switch button located on top of the unit. 

Keep  this  button  pressed  during  phase  sequence  or  open
phase  check.  When  the  push  switch  button  is  released  it
immediately goes off.

Reviews: