Chapter 1 Functional overview
KEW 2062/2062BT
- 7 -
KEW 2062/2062BT
Chapter 1 Functional overview
KEW 2062 / 2062BT is an advanced clamp power meter that is able to analyze the
harmonics for power quality check and verify phase sequences of power sources in various
wiring systems: of course, it can perform voltage/ current (in RMS) and power
measurements.
KEW 2062BT has Bluetooth communication function to connect itself with Bluetooth devices,
like a tablet, for remote monitoring and data saving.
Safety Construction
Designed to meet the international safety standard IEC 61010-1 CAT IV 300 V/ CAT III 600
V/ CAT II 1000V.
Wiring configuration
KEW 2062 / 2062BT supports: Single-phase 2-wire (Single-phase 3-wire), Three-phase
3-wire (two-wattmeter method), and Three-phase 4-wire.
Large-diameter clamp sensor
The current clamp sensor is able to clamp onto a wire up to 55mm in diameter.
Measurement and calculation
KEW 2062 / 2062BT can measure and calculate voltage, current, active/ reactive/ apparent
power, power factor, voltage-current phase differences, and frequency. (TRMS display)
Harmonics measurement
It is possible to measure and show each voltage/ current harmonic from 1st to 30th (in
RMS.), content rate, and total distortion factor (THD-R/THD-F).
Phase detection
This function is to verify phase rotation and missing phases of power source.
Application
Measured results and waveform data can an be transferred to tablet devices or
smartphones using Bluetooth (KEW 2062BT only). Special application “KEW
Power*(asterisk)” is available for reviewing the measured data.
KEW 2062/2062BT
Chapter 2 KEW 2062 / 2062BT
features
KEW 2062/2062BT
- 8 -
Chapter 2 KEW 2062 / 2062BT features
①
Current sensor
②
Trigger (to open/ close the jaws)
③
Barrier
Provides protection against electrical shock and
ensuring the minimum required clearance and
creepage distances. Always keep your fingers behind
the barrier.
④
Function switch
Turn and select the desired measurement function.
This switch also works as power switch: set it to
“OFF” to turn off the instrument.
⑤
Data hold switch
Holds the displayed readings. The LCD shows “ ”
symbol while the result is being held in the display.
⑥
Mode button*
1, 2
Toggles the displayed results in the sequences:
MAX: maximum value -> MIN: minimum value ->
AVG: average value -> |PEAK|: crest factor
(absolute value).
⑦
Backlight button
[
◄
]*
2
A long press turns on/ off the backlight.
⑦⑧
Item switching button
[◄►]
*
A short press toggles displayed items in sequences.
*1
Function ranges, related to current measurements, are
fixed while the LCD is showing MAX/ MIN/ AVG/ |PEAK|
(absolute value). The auto-ranging function is reactivated
when switching the display to instantaneous value.
*
2
Buttons
⑥
to
⑧
,
⑦
excluded, work differently
depending on the selected measurement function. For
further detail, see
clause 3.2 Buttons and switches, P. 9
,
and explanations about each function.
⑨
LCD
Field effect LCD with backlight
⑩
AC voltage input terminal
Connect the plug
⑪
of test lead (M-7290) to the corresponding terminal depending on the
wiring configuration to be tested.
⑪
Plug
⑫
Alligator clip
①
③
⑤
②
④
⑥
⑨
⑦
⑧
⑫
⑪
⑩
www.
.com