KwiKool CeilingMaster KCA Series Operation Manual Download Page 10

Page 8

External Alarm Signal Connections

 - All KCA/KCW units are equipped with an alarm 

signal output relay type (Form-C, normal open dry contacts), which can be used for 
monitoring basic unit failure functions. Relay contactor (no connector) is closed when 
the following condition has occurred:

I.

Condensate Tank Overflow

High Pressure Switch Closed

Low Pressure Switch Engaged

Cooling Function Fails

1.

2.

3.

4.

The output of the relay is rated at 5A at 30VDC or 5A at 250VAC (resistive load). This 
can be used to connect output is compatible with various warning devises such as 
alarm speakers, light indictors, etc.
Alarm contacts are labeled A1 and A2 on the external terminal block. Connect the 
warning device to these terminals.
The recommended warning signal wire size is 16AWG to 26AWG for a solid or 
stranded wire.

Fire Alarm Control Panel or Emergency Shut Off Connection

 - The KCA/KCW unit is 

equipped with a normally closed circuit which can be used to shut down the unit in a fire 
or emergency situation. Opening this circuit will shut the unit down and will not come 
back on until the circuit is reclosed.

J.

Connecting Fire Alarm Control Panel or EPO (Emergency Power Off) to KCA/KCW

 - 

First remove the jumper from the S1 and S2 terminals of the external terminal block. 
Connect the fire alarm signal wires or EPO wires to your KCA/KCW on the S1 and S2 
terminals on the external terminal block. Test functionality.
The recommended fire alarm signal wire size is 16AWG to 26AWG for a solid wire, or 
16AWG to 22AWG for a stranded wire. This function is used for test purposes and 
verification.

K.

Ducting for use with Typical Drop Ceiling

 - Ducting for both supply and return 

including a filter grill with filter will need to be supplied by the installer. All ducting 
should be of the insulated type to prevent condensation from forming on the duct and 
dripping on or around the installation. All duct should keep an bends to a minimum and 
should be the largest radius possible. Make sure that all ducts are properly secured to 
maintain proper airflow and integrity of the cooling section. Avoid sharp bends and try 
to make air ducts travel in a straight line for best performance.

L.

Insulated supply duct(s)

Filter return air grill with a filter for evaporator air intake

Diffuser(s) for cold air

Duct clamps

1.

2.

3.

4.

The following field supplied items are required:

CAUTION: DO NOT OPERATE UNIT WITHOUT A FILTER INSTALLED IN THE RETURN 

AIR FILTER GRILL

Summary of Contents for CeilingMaster KCA Series

Page 1: ...KCA KCW Operation Manual CEILING MASTER...

Page 2: ......

Page 3: ...roper usage and all safeguards This manual should be retained for future reference Section I Unit Components Page 3 Section II KCA KCW Standard Features Page 3 Section III Introduction Page 4 Section...

Page 4: ......

Page 5: ...PO emergency power off N O connection Automatic shut off with alarm signal output and audible alarm for C D E Condensate Pump High Pressure Switch Activation Low Pressure Switch Activation 1 2 3 Legen...

Page 6: ...for use or misuse of unit improper installation or failure to follow local building codes V Installation Things you will need for installation B Before you begin installation it is important to verify...

Page 7: ...maximum flexibility is installation methods Vibration isolation is required but can be installed on the unit or on the attachment to the building structure One common installation method and one that...

Page 8: ...ctor and run the wire into the electri cal box Strip the ends of the wires and install the appropriate connectors to the 3 wires for single phase units and 4 wires on the 3 phase models Attach to the...

Page 9: ...water level at the drain No dripping from the drain hose at the clamping area G Wall Thermostat Connection Preparation for thermostat connection H Use with a single stage wall thermostat Type standar...

Page 10: ...re Alarm Control Panel or EPO Emergency Power Off to KCA KCW First remove the jumper from the S1 and S2 terminals of the external terminal block Connect the fire alarm signal wires or EPO wires to you...

Page 11: ...he 3rd party thermostat is connected properly to unit and secured to the wall D Test Operation E Check operation with wall thermostat Set wall thermostat to FAN ON or FAN ONLY mode Fan should engage w...

Page 12: ...al factory jumper and retest Condenser Blocked Make sure that the condenser inlets and outlets are not blocked Verify that the condenser intake air is not overheated due to lack of ventilation or cond...

Page 13: ...Switch Actuated Potentially low on refrigerant Call a qualified technician since this is not user serviceable Condensate Pump Overflow Check to make sure condensate line is not kinked or obstructed I...