EC-05
3
4.3
Start potentiometer
:
Starter cranking timer
Setting range
:
1
10 secs. (stepless adjustment)
4.4
Time between start attempts
:
6 secs. (not
adjustable)
4.5
Engine start attempts
:
3 times (not adjustable)
SECTION 5 : LED STATUS INDICATORS
5.1
Engine Running Indicator LED (Green)
Flashing
:
Engine is in Standby mode
Illuminated
:
Engine is running
5.2
Engine Start Failure Indicator LED (Red)
When three engine cranking attempts have been
made but the engine will still not start normally
the Engine Start Failure indicator will illuminate,
indicating that the engine has failed to start.
Precaution
:
If AC voltage input is lost when the genset is
running normally the Engine Running and Engine
Start Failure indicators will flash at the same time.
This indicates that the system has failed but the
controller will not stop the engine. This situation
could be caused by an AVR failure or poor
connection of the AC voltage input.
Do not allow a remote start input signal to attempt
start automatically before the fault is eliminated.
This is to avoid possible improper operation of
the controller caused by loss of sensing of AC
frequency leading to repeated start attempts
even if the engine is running.