EC-05

 

SECTION 1 : SPECIFICATION 

DC Power Input

 

Static Power Consumption 

  Voltage 

 36 Vdc 

  Less than 0.2 watts 

  Fuse Spec. 

5 x 20mm S505-10A slow-blow 

 

 

Operating Environment 

AC Power Input

 

  Operating Temperature  -20 to +7

0 ˚C 

  Voltage 

 300 Vac single-phase 

  Relative Humidity 

Max. 90% 

  Frequency 

50 / 60 Hz 

  Vibration 

5.5 Gs @ 60 Hz 

 

 

Start Signal Output

 

Dimensions

 

  7 Amps @ 12 / 24 Vdc (Battery 

“+” terminal) 

  107.0 (L) x 75.0 (W) x 28.0 (H) mm

 

 

  4.21 (L) x 2.95 (W) x 1.10 (H) inch 

Stop Signal Output

 

 

  7 Amps @ 12 / 24 Vdc (Battery 

” terminal) 

Weight

 

 

  170 g +/- 2% 

Choke Signal Output

 

  0.37 lb +/- 2% 

  7 Amps @ 12 / 24 Vdc (Battery 

“+” terminal) 

 

 

SECTION 2 : PRODUCT OVERVIEW 

The EC-05 Auto Start Module can accept signals from 
a  remote  switch  or  an  ATS  to  automatically  start  and 
stop  a  gasoline  engine  generator  and  obtain  remote 
operation.  It  is  suitable  for  key  start  gasoline  engine 
generator  equipped  with  a  starter  motor  but  without 
automatic  start  and  stop  function.  The  EC-05  control 
module has choke control function making it especially 
suitable for use in cold regions. 

 

SECTION  3  :  EXTERNAL  WIRING  AND 
PRECAUTIONS 

3.1 

AC Input Terminals

Generator AC Power Input 

Terminals. The controller cuts off the signal to the 
starter  motor  when  AC  power  frequency  is 
greater than 18 Hz. 

 

Input Range

– 305 Vac 50/60 Hz 

 

 

Precautions

 

The AC Power Input must come directly from the 
generator  and  cannot  be  connected  and 
disconnected by a circuit-breaker. This is to avoid 
possible  improper  operation  caused  by  the 
controller  from  loss  of  sensing  of  AC  frequency 
leading to repeated start attempts even if engine 
is running. 

 

3.2 

B+  &  B-  Terminals

Battery  positive  (+)  and 

negtive (

–) power input terminals. 

 

Input Range

 36 Vdc 

 

 

Precautions

 

The  battery  must  not  be  disconnected  when  the 
generator  is  running.  This  is  to  avoid  the  high 
voltage  output  of  charging  alternator  being  fed 
directly into the controller and damage it. 

3.3 

Start  Terminal

Starter  motor  signal  output 

terminal.  Terminal  output  is  the  battery  (+)  of 
DC12V / 24V when the engine is cranking. 

 

3.4 

Stop  Terminal

Engine  stop  signal  output 

terminal.  During  engine  shutdown  the  terminal 
output  is  the  battery  (

).  When  the  Stop  timer 

setting  has  been  reached  this  terminal  is 
de-energized. 

 

3.5 

Choke Terminal

Choke Solenoid signal output 

terminal.  Terminal  output  is  the  battery  (+)  of 
DC12V / 24V when the engine is cranking. 

 

3.6 

Remote  Start  Terminals

Engine  Remote  Start 

Signal  input  terminals.  When  the  contact  is 
closed the engine is running. When the contact is 
open the engine is stopped. 

 

 

Precautions

 

The  external  remote  start  input  must  be  a  dry 
contact  without  power.  Inputting  a  DC  or  AC 
signal may cause damage to the controller. 

 

SECTION  4  :  TIME  DELAY  AND  FUNCTION 
SETTINGS 

4.1 

Stop potentiometer

Stop action timer. 

 

Setting range

 20 secs. (stepless adjustment) 

 

4.2 

Choke potentiometer

Choke action timer. 

 

Setting range

 20 secs. (stepless adjustment) 

 