background image

 

___________________________________________________________________________________________ 

4

 

EA45A220

 

 

Solution 2 : Install Kutai automatic flash module 
EB500 

 

G

~

Field

T

S

R

BATT.

FIELD

POWER

EA45A220

220VAC

F-

F+

B+

B-

-

+

EB500

F-

F+

B+

B-

ACC1

ACC2

fuel switch(N.O.) 

BATT.

Oll pressure or

 

 
 
 
 
 
 
 

WARNING

 

This  Automatic  Voltage  Regulator  is  not 
equipped with loss-Sensing Protection function / 
Over 

Excitation 

Protection. 

An 

additional 

Over-Voltage  Protection  device  for  load  may  be 
required  to  avoid  possible  damage  to  the 
equipment or severe personal injury or death. 

 

ATTENTION 

1.  AVR installation should only be performed by 

a qualified technician. 

2.  Install  AVR inside the generator control panel 

to  avoid  high  temperature,  moisture,  and 
location where AVR cannot be easily reached. 

3.  AVR  heat  sink  may  reach  a  high  temperature 

(above  60 

˚C)  when  AVR  is  powered,  do  not 

touch or ground AVR heat sink. 

4.  Make  sure  you  have  read  and  understand  the 

contents  of  the  instruction  manual  prior  to 
installation.  Incorrect  wiring  connection  may 
result  in  irreversible  damage  to  the  product 
and other equipments. 

 

SECTION 6 : TROUBLE SHOOTING 

SYMPTOM 

POSSIBLE CAUSES 

SOLUTIONS 

Voltage does not 

build up 

Residual voltage below 5

 

Vac

 

Field flash is required 

Incorrect wiring

 

Check wiring diagram for proper connection

 

Engine under speed

 

Increase engine speed to above 25 Hz

 

Carbon brushes were worn out 

Replace with new carbon brushes 

Low output voltage 

Voltage set point is not properly adjusted 

Adjust  VOLT  POT  clockwise  to  reach 
desired voltage 

External voltage adjusted too low 

Turn  the  external  VR  to  reach  desired 
voltage 

Under Frequency Protection is activated 

Refer to Section 4

 

Frequency selection and 

knee point adjustment 

Over output voltage 

Voltage set point is not properly adjusted 

Adjust  VOLT  POT  anti-clockwise  to  reach 
rated voltage 

Output voltage 

unstable (Hunting) 

Stability range is not set properly 

Refer to Section 2 Adjustment 

Field voltage or field resistance is too low 

Connect  suitable  resistor  in  series  to 
increase total resistance 

 

Appearance and specifications of products are subject to change for improvement without prior notice. 

Figure 7 

Summary of Contents for EA45A220 Series

Page 1: ...arters No 3 Ln 201 Qianfu St Qianzhen Dist Kaohsiung City 80664 Taiwan EA45A220 Generator Automatic Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator 45 Amp AVR for Carbon Brush Type Generators EA45A220HL Half Wave EA45A220FL Full Wave Parallel version is available for option ...

Page 2: ...EA45A220HL 4 5 kgs 2 External Volts Adjustment EA45A220FL 5 2 kgs 2 6 189 0 330 0 180 0 160 0 169 0 12 Unit mm 150 0 SECTION 2 ADJUSTMENT POWER LAMP Lights up when AVR is powered VOLT Voltage Adjustment Generator output voltage adjustment AUTOMATIC VOLTAGE REGULATOR U F LAMP POWER LAMP F S HI LO STAB VOLT U F STAB Stability Adjustment Correct stability adjustment must be conducted while the genera...

Page 3: ...e U F POT counter clockwise until the voltage starts to decrease U F lamp illuminates re adjust engine speed to rated speed SECTION 5 FIELD FLASHING When the regulator is installed correctly but the generator is failed to generate power Besides carbon brushes were worn out here are two possible causes below 5 1 The polarity of field is inverse Solution Exchange the connection of F and F 5 2 The re...

Page 4: ...nstallation Incorrect wiring connection may result in irreversible damage to the product and other equipments SECTION 6 TROUBLE SHOOTING SYMPTOM POSSIBLE CAUSES SOLUTIONS Voltage does not build up Residual voltage below 5 Vac Field flash is required Incorrect wiring Check wiring diagram for proper connection Engine under speed Increase engine speed to above 25 Hz Carbon brushes were worn out Repla...

Reviews: