EA341

 

4.6 

Excitation (EXC) Adjustment 

This  adjustment  is  set  and  sealed  in  the  works  and 
should  not  be  tampered  with.  An  over  excitation 
condition is indicated by the illumination of the red LED 
which  also  indicates  under-speed  running  and 
over-volt. 
 
The  generator  must  be  stopped  to  reset  an 
over-excitation trip. 

 
4.7 

DIP Adjustment 

This  feature  is  mostly  used  when  the  generator  is 
coupled  to  turbo  charged  engines  with  limited  block 
load  acceptance.  The  feature  works  by  increasing  the 
V/Hz slope to give greater voltage roll off in proportion 
to speed. 

With the DIP control fully anti-clockwise, the generator 
voltage  will  follow  the  normal  V/Hz  line  as  the  speed 
falls below nominal. Turning the DIP control clockwise 
provides greater voltage roll off aiding engine recovery. 

 

WARNING 

Please  make  sure  you  have  read  and  understand 
the  contents  of  the  instruction  manual  prior  to 
installation.  Incorrect  wiring  connection  may 
result  in  irreversible  damage  to  the  product  and 
other equipments.

 

 
 

 

SECTION 5 : FITTING AND OPERATING (Refer to generator wiring diagram for connection 

details) 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

ATTENTION 

1. AVR can be mounted directly on the engine, genset, switchgear, control panel, or any position that will 

not affects operation. For dimension reference, please see Figure 1. 

2. All voltage readings are to be taken with an average-reading voltmeter Meggers and high-potential test 

equipment must not be used. Use of such equipment could damage the AVR. 

3. Improper  setting  of  under-frequency  protection  could  cause  the  output  voltage  of  the  unit  to  drop  or 

become  unstable  under  with  changes  in  load.  Avoid  making  any  changes  to  the  U/F  setting  unless 
necessary. 

4. Set the O/E potemtiometer at max. position when paralleling.

 

 

Figure 1

 

Outline Drawing

 

DIP

EXC. TRIP

STABILITY

DROOP

TRIM

VOLT

UFRO

LED

C B A

C-A < 90KW
C-B < 90-550KW
B-A < 550KW

115.0

135.0

130.

0

150.

0

48.0

21.5

 5.5

 

Summary of Contents for EA341

Page 1: ...Qianfu St Qianzhen Dist Kaohsiung City 80664 Taiwan EA341 Generator Automatic Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator Compatible with Newage MX341 All manufacturer names and numbers are used for reference purpose only and do not imply that any part is the product of these manufacturer ...

Page 2: ...al Voltage Thermal Drift Less than 3 at temperature range 40 to 70 C Soft Start Ramp Time 2 seconds 10 Environment Operating Temperature 40 to 70 C Static Power Dissipation Storage Temperature 40 to 85 C Max 12 watts Relative Humidity Max 95 Vibration 3 3 Gs 100 2K Hz Analogue Voltage Input Input Resistance 1K ohm Dimensions Max Input 5 Vdc 150 0 L x 135 0 W x 48 0 H mm Sensitivity 1V for 5 genera...

Page 3: ...ection to allow parallel running with other similarly equipped generators NOTE 1 Derate linearly from 3 7A at 50 C to 2 7A at 70 C 2 The stated voltage regulation may not be maintained in the presence of certain transmitted radio signals Any change in regulation will fall within the limits in Criteria B of S EN 61000 6 2 2001 3 After 10 minutes 4 Applies to Mod status E onwards Generator de rate m...

Page 4: ...e stability control anti clockwise until the generator voltage starts to become unstable The optimum or critically damped position is slightly clockwise from this point i e where the machine VOLT are stable but close to the unstable region 4 3 Under Frequency Roll Off UFRO Adjustment 4 3 1 The AVR incorporates an under speed protection circuit which gives a VOLT Hz characteristic when the generato...

Page 5: ...RNING Please make sure you have read and understand the contents of the instruction manual prior to installation Incorrect wiring connection may result in irreversible damage to the product and other equipments SECTION 5 FITTING AND OPERATING Refer to generator wiring diagram for connection details ATTENTION 1 AVR can be mounted directly on the engine genset switchgear control panel or any positio...

Page 6: ... A2 S1 S2 J1 J2 J3 J4 J5 J6 J7 J8 K2 K1 P2 P3 P4 XX X 3 2 2 1 FREQUENCY SENSING SELECTION INDICATOR C B A 3 2 1 STABILITY DIP LED SELECTION k1 k2 linked for normal operation 3 1 4P 60HZ 3 2 4P 50HZ 2 1 6P 50HZ NO LINK 6P 50HZ C A 90KW EA341 G Generator P4 P3 P2 PMG X XX 3 Bridge T 220V S R S1 C T S2 1 2 For external adjusted 1K 2 3 Exciter Figure 2 Disposition Drawing Figure 3 Wiring Drawing Note ...

Reviews: