background image

 
 

______________________________________________________________________________________ 

EA04C

 

3

 

3.  Ensure proper fuse is installed. 

4.  Turn  voltage  and  stability  potentiometer  full 

anticlockwise (lowest voltage level). 

5.  If used, turn external voltage potentiometer to the 

middle position. 

6.  Use  600  VAC  Voltage  meter  connect  to  AC 

output terminal and measure the output voltage. 

5.2  Startup Procedure 

1.  To  start  and  run  the  generator  at  no  load  and 

rated  speed.  The  generator  output  voltage 
should build up to a minimum level if the voltage 
does  not  build  up,  It  may  cause  by  low  residual 
voltage  of  generator.  Refer  to  field  flashing 
section in generator manual. 

2.  Slowly  adjust  voltage  potentiometer  until  the 

generator voltage reach the proper value. 

6.  STABILITY ADJUSTMENTS 

1.  Slowly  rotate  the  STAB  control  in  the  clockwise 

(CW)  direction  will  change  the  AVR  and 
generator

’s  response  time,  if  over  adjusted  the 

voltage  will  become  unstable,  if  under,  the 
instant 

heavy 

load 

voltage 

will 

change 

significantly. 

2.  It is advised to use a voltmeter DCV to adjust the 

STAB control F+, F

– until the oscillate becomes 

minor. By doing so helps to improve and reduce 
the voltage change under heavy load. 

7.  FIELD FLASHING 

When  the  regulator  is  operated  with  the  generator 
for  the  first  time,  the  polarity  residual  magnetism 
may not correct or the magnitude not enough. If the 
generator does not build-up after startup, shut down 
the  prime  mover  and  proceed  with  the  following 
steps : 

1.  With the prime mover at rest, apply a dc source 

(not  grounded)  of  not  more  than  12V,  to 
terminals  F+  (positive)  and  F

–  (negative)  in 

series with a limiting resistor of 3 ~ 5 ohms. 

2.  Allow  approximately  3 seconds before removing 

the dc source. 

3.  Start  prime  mover  and  measure  voltage  at 

regulator leads 3 and 4. If voltage is greater then 
5  volts,  voltage  build-up  should  be  successful. 
Repeat  field  flashing  procedure  if  less  than  6V 
residual is measured. 

4.  If  repeating  steps  1  and  2  does  not  result  in 

generator  voltage  build-up,  replace  the  voltage 
regulator. 

WARNING 

Please  make  sure  you  have  read  and 
understand  the  contents  of  the  instruction 
manual  prior  to  installation.  Incorrect  wiring 
connection  may  result  in  irreversible  damage 
to the product and other equipments.

 

 

 

V

olt

EXT VR

FUS

E

5A

SW

S

ta

b

FUSE

VR

EXT

Volt

SW

Stab

F-

3

F+

4

P

 

 

 

(% O

F NO

MI

NA

L)

GE

NERA

TO

R O

UT

PUT

 VO

LT

AG

E

0

40

20

60

10

20

30

40

60

50

80

100

120

50HZ

60HZ

FREQUENCY (HZ)

 

 

 

 

Outline dimension 

Figure 1 

Frequency compensation curves 

Figure 2 

UNIT : mm 

Summary of Contents for EA04C

Page 1: ... Qianzhen Dist Kaohsiung City 80664 Taiwan EA04C Generator Automatic Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator Compatible replacement for Basler VR63 4 VR63 4A and Marathon SE100A Use for reference only and not genuine Basler product Use with Kutai EP200 Paralleling Module for parallel operation ...

Page 2: ... 3mm H Weight 175 g 2 2 WIRING Refer to Figure 3 Power input 3 4 Sensing input 4 P F F Exciter EXT VAR External Voltage Adjustment 3 FREQUENCY COMPENSANION The frequency compensation characteristic to improve system load pickup performance by restraining voltage recovery until frequency has also started to recover For 50Hz system the regulator is preset at the factory for a 45Hz corner frequency F...

Page 3: ...mprove and reduce the voltage change under heavy load 7 FIELD FLASHING When the regulator is operated with the generator for the first time the polarity residual magnetism may not correct or the magnitude not enough If the generator does not build up after startup shut down the prime mover and proceed with the following steps 1 With the prime mover at rest apply a dc source not grounded of not mor...

Page 4: ...1 Sensing voltage selector ON for 220V OFF for 380 480V 2 SW 2 Frequency selector ON for 50Hz OFF for 60Hz 3 SW 3 Response ON for fast OFF for slow Use only original supplied spare protection fuse for fuse replacement Please accept our sincere apology if any modification in performance specification or appearance is made without prior notice SW 1 OFF for 380 480VAC system 3Ø 4W 380 480 VAC Figure ...

Reviews: