CH36 

SECTION 1 : SPECIFICATION 

Power Input 

Protection 

 

Voltage 

100 

 277 Vac 

 

Constant  output  voltage,  limited  charge  current 

reverse polarity & short circuit protections. 

 

Frequency 

47 

 63 Hz 

 

 

DC Output 

Environment 

 

CH3612 

13.8 Vdc / 6A Max. 

 

Operation Temperature 

-20 

 +60 ˚C 

 

CH3624 

27.6 Vdc / 3A Max. 

 

Storage Temperature 

-30 

 +80 ˚C 

 

 

Relative Humidity 

Max. 90% 

DC Voltage Regulation 

 

Vibration 

1.5 Gs @ 5 

 30 Hz 

 

<

 

+/- 1% 

 

5.0 Gs @ 30 

 500 Hz 

 

 

Charge Mode 

Mounting Type 

 

Float 

Panel Mount or DIN Rail *

1

 

 

 

Efficiency 

Dimensions 

 

> 80% @ Full load 

 

159.0 (L) x 112.0 (W) x 66.0 (H) mm 

 

 

Low Battery Voltage Alarm Output Capacity 

Weight 

 

0.5A @ 40 Vdc 

 

0.67 Kg +/- 2% 

 

 

Suitable Battery Type 

 

 

Gel, Flooded Lead Acid & AGM 

*

1

 

Optional DIN Rail Mounting Kit is sold separately 

SECTION 2 : INSTALLATION AND OPERATION 

2.1  Make  sure  that  the  correct  battery  charger  is 

selected for your battery. 

 
2.2  Check correct line power for the battery charger. 
 
2.3  Connect  line  voltage  to  the  charger,  then  the 

“ power indicator ” should be lit up and display will 
show  the  output  voltage  and  current,  the  DC 
output voltage be as follow : 

 

CH3612

13.8 Vdc +/- 1% 

 

CH3624

27.6 Vdc +/- 1% 

 
2.4  AC  power  off  before  connect  the  charger  DC 

output to battery leads “+ & -”. 

 
 

Caution!!  Crimp  and  property  secure  terminal 
lugs on to power wires to avoid shorts. 

 
2.5  Turn on AC power, battery charger will charge the 

battery with an automatic adjusted current related 
to battery  voltage  and cyclically displays charging 
voltage and current on screen. 

 
2.6  Floating charge mode with current-limiting function 

built-in.  Charger  can  remains  connected  during 
engine cranking heavy load condition. 

 
 

2.7  For CH3612, minimum battery voltage must higher 

than 6 Vdc or the battery charger will automatically 
shut-down  and  all  the  indicators  on  the  panel  will 
be  went  out.  (  For  CH3624,  the  minimum  battery 
voltage is 12 Vdc ). 

 
2.8  Voltage  sensing  circuit  automatically  stops 

charging battery when the battery is fully charged. 

 

2.9  Input  and  output  connection  cable  size 

 

1.25mm² (AWG 16). 

 

SECTION 3 : 

LOW DC 

VOLTAGE

 ALARM 

For CH3612 when battery volt less than 10 Vdc 

For CH3624 when battery volt less than 20 Vdc 
 
“ Low DC indicator ” will be lit up with solid state 0.5A 
battery negative alarm output. 

Low  DC

Battery

+

Low DC Alarm Indicator

( Relay or buzzer can also be used )

 