CH36
SECTION 1 : SPECIFICATION
Power Input
Protection
Voltage
100
−
277 Vac
Constant output voltage, limited charge current
reverse polarity & short circuit protections.
Frequency
47
−
63 Hz
DC Output
Environment
CH3612
13.8 Vdc / 6A Max.
Operation Temperature
-20
−
+60 ˚C
CH3624
27.6 Vdc / 3A Max.
Storage Temperature
-30
−
+80 ˚C
Relative Humidity
Max. 90%
DC Voltage Regulation
Vibration
1.5 Gs @ 5
−
30 Hz
<
+/- 1%
5.0 Gs @ 30
−
500 Hz
Charge Mode
Mounting Type
Float
Panel Mount or DIN Rail *
1
Efficiency
Dimensions
> 80% @ Full load
159.0 (L) x 112.0 (W) x 66.0 (H) mm
Low Battery Voltage Alarm Output Capacity
Weight
0.5A @ 40 Vdc
0.67 Kg +/- 2%
Suitable Battery Type
Gel, Flooded Lead Acid & AGM
*
1
Optional DIN Rail Mounting Kit is sold separately
SECTION 2 : INSTALLATION AND OPERATION
2.1 Make sure that the correct battery charger is
selected for your battery.
2.2 Check correct line power for the battery charger.
2.3 Connect line voltage to the charger, then the
“ power indicator ” should be lit up and display will
show the output voltage and current, the DC
output voltage be as follow :
CH3612
:
13.8 Vdc +/- 1%
CH3624
:
27.6 Vdc +/- 1%
2.4 AC power off before connect the charger DC
output to battery leads “+ & -”.
Caution!! Crimp and property secure terminal
lugs on to power wires to avoid shorts.
2.5 Turn on AC power, battery charger will charge the
battery with an automatic adjusted current related
to battery voltage and cyclically displays charging
voltage and current on screen.
2.6 Floating charge mode with current-limiting function
built-in. Charger can remains connected during
engine cranking heavy load condition.
2.7 For CH3612, minimum battery voltage must higher
than 6 Vdc or the battery charger will automatically
shut-down and all the indicators on the panel will
be went out. ( For CH3624, the minimum battery
voltage is 12 Vdc ).
2.8 Voltage sensing circuit automatically stops
charging battery when the battery is fully charged.
2.9 Input and output connection cable size
≧
1.25mm² (AWG 16).
SECTION 3 :
LOW DC
VOLTAGE
ALARM
For CH3612 when battery volt less than 10 Vdc
For CH3624 when battery volt less than 20 Vdc
“ Low DC indicator ” will be lit up with solid state 0.5A
battery negative alarm output.
Low DC
Battery
+
Low DC Alarm Indicator
( Relay or buzzer can also be used )