![Kutai electronics ATS-380 Operator'S Manual Download Page 13](http://html.mh-extra.com/html/kutai-electronics/ats-380/ats-380_operators-manual_2012543013.webp)
ATS-380
Automatic Transfer Switch
______________________________________________________________________________________
13
4.6 Specification Summary
PARAMETER
SPECIFICATION
Input Control Voltage
280 VAC to 480 VAC 50/60 Hz
Voltage Measurement Range
280 VAC to 480 VAC 50/60 HZ
Frequency Measurement Range
40HZ to 70HZ
Generator Start Relay
7A @ 250VAC Max
Transfer to Normal Relay
7A @ 250VAC Max
Transfer to Standby Relay
7A @ 250VAC Max
Auxiliary Relay
0.5A @ 120VAC
1.0A @ 24VDC
Operating Temperature
-20
°
C ~ 70
°
C
Storage Temperature
-35
°
C ~ 85
°
C
Operating Humidity
0 to 95% relative humidity
SECTION 5 : INSTALLATION INSTRUCTIONS
5.1 General
The ATS-380 controller has been designed for front panel mounting.
5.2 Panel Cut-Out ( All Dimensions in MM. )