ATS-380
Automatic Transfer Switch
______________________________________________________________________________________
12
*
*
*
*
LINE BY LINE PROGRAMMING TABLE
LINE
DESCRIPTION
VALUE
Factory
Setting
1
System voltage setting ( 250V ~ 500V )
Key in the real volt of normal side R & T
380V
2
Is this ATS operator in 1Ø or 3Ø
1) 1Ø 2) 3Ø
2
3
Selected the Switch type of ATS
1) MCCB type
2) Double throw type
3) Magnetic contactor type
1
4
Plant Manual test with or without load
1) Test without load 2) Test with load
2
5
TDEN – Time delay emergency to normal
0 ~ 60 ( 0 ~ 300sec )
2
(10sec)
6
TDNE – Time delay normal to emergency
0 ~ 60 ( 0 ~ 300sec )
2
(10sec)
7
TDES – Time delay engine start
0 ~ 06 ( 0 ~ 30sec )
1
(5sec)
8
TDEC – Time delay engine cool-down
0 ~ 60 ( 0 ~ 300sec )
12
(60sec)
9
Normal source over voltage setting
39 ~ 48 ( 390V ~480V )
42
(420V)
10
Normal source under voltage setting
28 ~ 37 ( 280V ~ 370V )
34
(340V)
11
Time delay if there is a problem with normal
source voltage output
0 ~ 99sec
( 0 = Without voltage monitor function )
10 Sec
12
Normal source over frequency setting
51 ~ 70Hz
55Hz
13
Normal source under frequency setting
40 ~ 59Hz
45Hz
14
Time delay if there is a problem with normal
source frequency output
0 ~ 99sec
( 0 = Without freq monitor function )
10 Sec
15
Standby source over voltage setting
39 ~ 48 ( 390V ~480V )
42
(420V)
16
Standby source under voltage setting
28 ~ 37 ( 280V ~ 370V )
34
(340V)
17
Time delay if there is a problem with standby
source voltage output
0 ~ 99sec
( 0 = Without volt monitor function )
10 Sec
18
Standby source over frequency setting
51 ~ 70Hz
55Hz
19
Standby source under frequency setting
40 ~ 59Hz
45Hz
20
Time delay if there is a problem with standby
source frequency output
0 ~ 99sec
( 0 = Without freq monitor function )
10 Sec
21
Current day of week setting
1 ~ 7 (Mon to Sun)
current
22
Current hour setting
00 ~ 23
current
23
Current minute setting
00 ~ 59
current
24
Plant exerciser test day of week
1 ~ 7 (Mon to Sun)
6(Sat)
25
Plant exerciser hour
00 ~ 23
12
26
Plant exerciser minute
00 ~ 59
00
27
Engine run time on exerciser
0 ~ 60 min ( 0 = Without exerciser function )
0
28
Plant exerciser test with or without load
1) Without load
2) With load
1
29
Display mode setting
1) Cyclic mode
2) Fix mode
1
30
Auxiliary contactor feature (The contactor just
can define to one of the three features)
1) Transfer fail alarm 2) Pre-transfer signal
3) Pre-exerciser signal
2
31
Pre-transfer time delay before transfer load
from one source to another source
1 ~ 99 sec
10 Sec
32
Pre-exerciser
time
delay
before
engine
exerciser test
1 ~ 99 sec
10 Sec