ADVR-083

 

SECTION 1 : SPECIFICATION 

Sensing Input (E1, E2, E3) Average Reading 

Soft Start Ramp Time

 

  Voltage and Frequency DIP switch settings 

  4 s/- 10% 

  1 phase 

(E1, E2)

 / 3 phase 

(E1, E2, E3)

 

 

90 

 130 Vac @ 110 Vac 

Voltage Regulation

 

   

180 

 260 Vac @ 220 Vac 

  Less than +/- 0.5% (with 4% engine governing) 

   

340 

 520 Vac @ 440 Vac 

 

  Frequency 

50/60 Hz 

Typical System Response

 

 

  Less than 20 milliseconds 

Power Input (X1, X2, Z2)

 

 

  Voltage 

60 

 300 Vac, 1 phase / 3 phase 

EMI 

 

  1 phase ( X1, X2 ) / 3 phase ( X1, X2, Z2 ) 

  Built-in Harmonic suppression 

  Frequency 

40 

 500 Hz 

 

 

Static Power Dissipation

 

Auxiliary Input (Z1, Z2)

 

  Max. 6 watts   

  Voltage 

60 

 300 Vac, 1 phase 2 wire 

 

  Frequency 

40 

 500 Hz 

Under Frequency Protection (Factory Preset) 

 

  50 Hz system preset knee point at 45 Hz 

Excitation Output (F+, F-)

 

  60 Hz system preset knee point at 55 Hz 

  110V 1 phase Continuous 

63 Vdc 

8A 

 

   

Max. 90 Vdc 10A for 10 secs. 

Over Excitation Protection

 

  220V 1 phase Continuous 

125 Vdc  8A 

  25 

 105% of Input Power (adjust with EXC pot.) 

   

Max. 180 Vdc 10A for 10 secs. 

  O/E acts after 10 sec. delay. The OE function can be   

  220V 3 phase Continuous 

150 Vdc  8A 

  turned OFF by adjusting EXC. clockwise to max. 

   

Max. 215 Vdc 10A for 10 secs. 

 

  Resistance 

Min.15 ohms, Max.100 ohms @ 220V 

Voltage Thermal Drift 

  Fuse Spec. 

Slow blow 5 x 20 mm 10A 

  Less than 3% from -

40 to +70 ˚C 

 

 

External Voltage Adjustment (VR1, VR2)

 

Under-Frequency Knee Point Thermal Drift 

  Max. +/- 10%  @ 1K ohm 1 watt potentiometer 

  Less than +/- 0.1 Hz from -

40 to +70 ˚C 

 

 

Quadrature Droop Input (S1, S2) 

Environment 

  CT N:5A or N:1A (DIP switch setting) 

  Operation Temperature 

-40 to +60 

˚C 

  Burden : greater than 5VA 

  Storage Temperature 

-40 to +85 

˚C 

  Sensi/- 7% @ PF +/- 0.5 

  Relative Humidity 

Max. 95% 

  (Can be adjusted through Droop setting) 

  Vibration 

5.5Gs @ 60 Hz 

 

 

Analogue Voltage Input (A1, A2) 

Dimensions

 

  Input resistance greater than 2K ohms 

  150.0 (L) x 135.0 (W) x 61.0 (H) mm 

  Input Range +/- 5 Vdc    or    0 

 10 Vdc 

  5.91 (L) x 5.31 (W) x 2.40 (H) inch 

  Sensitivity Max.1 Vdc = 5% change in output voltage 

 

  (Can be adjusted through Trim setting) 

Weight

 

 

  750 g +/- 2% 

Build Up Voltage

 

  1.654 lb +/- 2% 

  Greater than 5 Vac, 25 Hz residual volts input power 

 

 

ATTENTION 

In order to avoid permanent damage to the AVR confirm that the voltage sensing input setting matches 
the generator before use (DIP switches SW5 and SW6) 

 

Summary of Contents for ADVR-083

Page 1: ...iwan ADVR 083 Universal Hybrid Analog Digital Voltage Regulator Operation Manual Analog Digital AVR Single phase Three phase Voltage detection 8 Amp Voltage Regulator for use with Auxiliary Winding PMG and self excited SHUNT brushless generators Can be used together with KUTAI Auxiliary Excitation Booster module to increase motor starting capacity of shunt generators ...

Page 2: ... Vdc 10A for 10 secs O E acts after 10 sec delay The OE function can be 220V 3 phase Continuous 150 Vdc 8A turned OFF by adjusting EXC clockwise to max Max 215 Vdc 10A for 10 secs Resistance Min 15 ohms Max 100 ohms 220V Voltage Thermal Drift Fuse Spec Slow blow 5 x 20 mm 10A Less than 3 from 40 to 70 C External Voltage Adjustment VR1 VR2 Under Frequency Knee Point Thermal Drift Max 10 1K ohm 1 wa...

Page 3: ..._____________________________________________________________________ ADVR 083 3 SECTION 2 OUTLINE SIZE INSTALLATION REFERENCE 130 0 5 12 150 0 5 91 21 5 0 85 61 0 2 40 135 0 5 31 115 0 4 53 5 5 0 22 Figure 1 Outline Drawing ...

Page 4: ... sensing set by DIP switch SW7 EXC Over Excitation Protection Adjustment 25 105 of Rated Excitation Adjustable Adjust EXC potentiometer clockwise to Max to turn OFF O E protection STAB Stability Adjustment Stability range set by DIP switches SW1 and SW2 U F Under Frequency LED Under Frequency Protection status ON Activated DIP U F Protection Voltage Slope Adjustment When U F protection is activate...

Page 5: ...d potentiometer 1k 1W External ADVR 083 G R S N T Field potentiometer 1k 1W External Figure 3 Self Excited SHUNT 110 220 Vac Single phase Three phase Figure 4 Self Excited SHUNT 440 Vac Single phase Three phase ADVR 083 G R S N T Field AUX wires potentiometer 1k 1W External ADVR 083 G R S N T Field potentiometer 1k 1W External Figure 5 Auxiliary Winding 110 220 440 Vac Single phase Three phase Fig...

Page 6: ...IVT 1270 2470 F F Figure 8 ADVR 083 IVT 1270 IVT 2470 Wiring Connection Self Excited SHUNT 110 220 Vac Single phase Three phase ATTENTION 1 Before using a Megger or a Withstand Voltage Tester remove the wires connecting to the AVR to prevent high voltage damage to the regulator 2 Improper setting of under frequency protection could cause the output voltage of the unit to drop or become unstable un...

Reviews: