                     Switch #1       Switch #2      Switch #3           Trips Below:

OFF

OFF

OFF

13.01 Volts

OFF

OFF

ON

12.76 Volts

OFF

ON

OFF

12.52 Volts

OFF

ON

ON

12.29 Volts

ON

OFF

OFF

12.07 Volts

ON

OFF

ON

11.85 Volts

ON

ON

OFF

11.64 Volts

ON

ON

ON

11.44 Volts

INTRODUCTION

The UV-OV Relay is a device which continuously monitors the voltage of a battery system and
detects overvoltage and undervoltage conditions. A set of contacts are provided for each of
these conditions. The values of the overvoltage and undervoltage detection points are easily
and independently programmable by accessible “DIP” switches behind the removable cover.
An adjustable time delay of 8 to 150 seconds is provided.

INSTALLATION
Figure 1 is a view of the programming switches with the snap-on top cover removed. Refer to
this figure when programming the unit.

Programming Switches

FIGURE 1

TEST/RUN

Switch

TEST

Undervoltage
Programming

Switches

Overvoltage

Programming

Switches

R U N

(a) Select the desired undervoltage trip point from the column to the far right in table 1 below.

(b) Set switches #1, #2 and #3 to the settings shown in table 1 corresponding to the
       selected trip point in step (a).

TABLE 1 Undervoltage Programming

Summary of Contents for 091-45

Page 1: ...RRANTY A BATTERY SYSTEM VOLTAGE MONITOR WHICH DETECTS OVERVOLTAGE AND UNDERVOLTAGE CONDITIONS AND PROVIDES A TIME DELAY FOR THE OUTPUT KUSSMAUL ELECTRONICS CO INC 170 CHERRY AVE WEST SAYVILLE N Y 11796 BOOK 09145004 OCTOBER 13 2000 TEL in NY 631 567 0314 TOLL FREE 800 346 0857 FAX 631 567 5826 ...

Page 2: ...age detection points are easily and independently programmable by accessible DIP switches behind the removable cover An adjustable time delay of 8 to 150 seconds is provided INSTALLATION Figure 1 is a view of the programming switches with the snap on top cover removed Refer to this figure when programming the unit Programming Switches FIGURE 1 TEST RUN Switch TEST Undervoltage Programming Switches...

Page 3: ...rip point in step c e Set switch 7 to RUN operation if it is not already in that position This allows approximately 1 second of time delay for the trip points to act and filters alternator ripple f For mechanical installation refer to figure 3 for the hole pattern and sizes g For electrical installation refer to figure 2 which shows the connections to various parts of the vehicle The alarm contact...

Page 4: ...MUM COUNTERCLOCKWISE 8 sec MID POSITION 80 sec MAXIMUM CLOCKWISE 150 sec FIGURE 3 A5 C 1 R1 A4 R2 R3 R17 R6 R16 C 3 C 2 A2 A7 R9 C 4 R8 Q 4 U1 A1 C R2 C R 1 U3 7808 R15 Q 3 DS3 Q 2 A6 U2 Q 1 DS1 R7 VR1 C R3 C R5 S1 K1 K2 10 9 8 7 6 5 4 3 1 2 J1 DS2 R10 R12 U4 R13 R11 R14 C R7 C R6 C R4 KUSSM AUL ELEC TRO NIC SC OIN C TDADJ B091 45 004 HI LO NO RM AL ...

Page 5: ...FIGURE 4 Alarm Lamp Connections Via Ground FIGURE 5 Alarm Lamp Connections Via 12 Volts ...

Page 6: ...SPECIFICATION OUTLINE 1 50 3 16 DIA 4 25 2 00 3 50 3 75 ...

Page 7: ...use within 3 years from the date the equipment was shipped Equipment is to be returned shipping charges prepaid and will be returned after repair shipping charges paid Kussmaul Electronics Company Inc shall have no liability for damages of any kind to associated equipment arising from the installation and or use of the Kussmaul Electronics Company Inc products The purchaser by the acceptance of th...

Reviews: