background image

AC VOLTS

FREQUENCY

AC AMPS #1

AC AMPS #2

ZERO AC AMPS #1

ZERO AC AMPS #2

f

 BACK

To calibrate the VAAFH meter volts, Hz. and Amps, you will 

need a separate reference test meter, AC RMS voltage and 

current probe to measure AC RMS current. All reference meters 

should have an accuracy of 1% or better. Also you will need a 

stable voltage and load source. Load source can be lamps or 

heaters. NOTE: These loads may drift a little so always re verify 

measurements before adjusting calibration value. Calibration 

should be performed after installation is complete.

Remove the cover from the VAAFH interface box to gain access 

to its terminal block. This will be needed to measure AC voltage. 

WARNING: High voltage is present at terminal block.

AC Volts

Apply AC mains and DC power to circuit. Do not apply a load 

at this time. Measure the AC RMS voltage at TB1 terminals 9 

and 10. Go to the sub-menu of the AC VOLTS calibration menu 

and adjust the value up or down using the up or down buttons 

so it matches the measured reading then press the 

*

 (accept) 

button when done.

Frequency

Frequency does not typically need calibration. If frequency 

needs calibration a frequency meter will be needed. Measure 

the frequency at TB1 terminals 9&10. Got to the sub-menu of 

the calibration frequency menu and adjust the value up or down 

using the up or down buttons then press the 

*

 (accept) button 

when done. WARNING: High voltage is present at  

terminal block.

Zeroing AC Amps #1 and #2

Apply AC mains and DC power to circuit. Do not apply any 

load at this time. Go to the sub-menu of the calibrate menu 

and select either the ZERO AC AMPS #1 or #2. Zeroing amps 

should be done before calibrating AC Amps.

AC Amps #1 and #2

Apply AC mains and DC power to circuit and apply a load. 

Measure the AC RMS current through the load wires (#1 or 

#2). Go to the sub-menu of the AC AMPS (#1 or #2) calibration 

menu and adjust the value up or down using the up or down 

buttons so it matches the measured reading then press the 

*

 

(accept) button when done.

ATTENTION

:

 Calibration should only be performed by 

qualified personnel. Published accuracies are based on proper 

calibration in conjunction with the 773-5385-0 meter interface. If 

it is determined that calibration is needed, first ensure all sense 

transformers are terminated properly to the meter prior  

to calibrating.

If the Amps show a positive number when zero amps are 

being passed through the current transformer it is possible to 

automatically zero the amps #1 or amps #2 from the “Calibrate” 

page. At low values of CT voltage there is a slight interaction 

between the Zero Amps and the 

Calibrate Amps and it may require you to re-calibrate slightly 

after you have used the Zero Amps feature.    

If the user accidentally zeros the amps #1 or amps #2 while 

positive amps are actually being passed through the current 

transformer, the meter will no longer display amps correctly 

and the amps offset will have to be cleared. This is done by 

holding the 

q

 key for more than 10 seconds while the meter 

is displaying “NO YES NO NO” on the “Setup”

g

”Reset Alarm 

Bell” page. This feature has been hidden to make it difficult to 

do by accident.  

Trying to calibrate the instrument when in simulate mode will be 

problematic since the simulated inputs are constantly changing.

F) Calibration DC

Selecting the CALIBRATE DC menu brings up the following 

sub-menu:

DC VOLTS

DC AMPS

ZERO DC AMPS

f

 BACK

DC Volts

Apply DC power to circuit. Do not apply a load at this time. 

Measure the DC voltage at interface terminal block, across 

(+)DCV and (-) DCV.  Go to the sub-menu of the DC VOLTS 

calibration menu and adjust the value up or down using the up 

or down buttons so it matches the measured reading then press 

the 

*

 (accept) button when done.

Zeroing DC Amps

Apply DC power to circuit. Do not apply any load at this time. 

Go to the sub-menu of the calibrate menu and select: ZERO 

DC AMPS. Zeroing DC amps should be done before calibrating 

DC Amps.

DC Amps

Apply DC power to circuit and apply a load. Measure the DC 

170 Cherry Avenue

West Sayville, NY 11796

www.kussmaul.com

Ph: 800-346-0857

Fax: 631-567-5826

[email protected]

5

Summary of Contents for 091-247

Page 1: ...he display can be remotely turned ON OFF All set up calibration and alarm values are saved to non volatile memory The system is complete with DC amp shunt voltage and current transformers and is facto...

Page 2: ...e at source To AC distribution panel 2 2 5 max 3 max CT 1 CT 1 CT 1 CT 2 CT 2 DC DC 5 VDC alarm N U VAC VAC L 1 L 1 Tie wrap wire hold down point White Orange Black Red Orange White DC Interface box L...

Page 3: ...AWG cable Wire colors used are black and red One end will have factory terminated QD s which can be connected to the Interface box see wiring diagram The opposite end must be terminated with ring lug...

Page 4: ...fter 60 seconds from the last key press For each menu or sub menu item the following is true Pressing the q or p keys moves highlighted selection down or up Pressing the QUIT key returns you to the Ma...

Page 5: ...d reading then press the accept button when done ATTENTION Calibration should only be performed by qualified personnel Published accuracies are based on proper calibration in conjunction with the 773...

Page 6: ...is ever forgotten the instrument can be reset back to factory default see Reset to Default Caution Resetting to factory default will reset all alarm and calibration settings as well B Zero Generator...

Page 7: ...system and causes the Main Page to be displayed SPECIFICATIONS Power Supply 9 50 to 33 00 VDC 100mA Operating Temperature 32 to 122 F 0 to 50 C Size 4 3 x 4 3 x 3 5 deep 110 x 110 x 89 mm Display Dat...

Reviews: