INTRODUCTION

The VAAFH AC/DC is an ideal monitor system for 240/120 

generators and grid power sources and provides monitor of 

load balancing on the 120 VAC legs. Additionally, the AC/

DC model now provides DC volts and amps monitoring.  This 

meter meets NFPA requirements 1901 22.4.6.3 for monitoring 

of permanently mounted generators on fire apparatus. 

It provides accurate digital metering for AC Volts, Amps, 

Frequency and logs generator hours. Low/High Voltage, 

Amperage and Frequency alarms are easily set. When 

activated, the built-in 85 dB alarm will sound and the affected 

display reading will change RED for the out-of-limit condition.  

The meter is waterproof and rugged with a large color LCD 

display screen read-out divided into 6 display sections allowing 

the operator quick, and accurate assessment on the state of 

the generator output and applied loads.

AC volts are displayed from 90 to 300 VAC and DC volts to 33 

VDC, 300 amps max.  Two Amperage readouts for both 120V 

legs of the 240 circuit are displayed from 0 to 150 amps, and 

Frequency is also displayed. Generator hours are logged and 

easily viewed via menu selection.

The meter is powered from 12-24VDC. Four levels of 

backlighting can be selected and the display can be remotely 

turned ON/OFF. All set-up, calibration and alarm values are 

saved to non-volatile memory. The system is complete with DC  

amp shunt, voltage and current transformers, and is factory 

calibrated to read within 1%. The large LCD display draws only 

0.08 amps with full brightness and only 0.02 in sleep mode. 

INSTALLATION

Before starting the installation, please read this entire  

section first

The meter is designed for panel mount in a 2-1/8 hole. 

Locate a suitable position for the meter, (refer to applicable 

NFPA regulations) cut mounting hole  2-1/8” (55mm) where 

you desire to mount the instrument (Figure 1) and secure 

in position, the gasket provided ensures a waterproof seal 

against the mounting surface. (Caution it’s important that the 

spacing nuts (2) contact the underside of the mounting bracket. 

Do not over tighten the mounting nuts). Finger tighten the 

screws that mount the instrument bracket. It is not necessary 

or recommended to use tools.

MOUNTING (Figure 1)

Finger Tighten Meter Hardware Only - Do Not Use Tools

Bulkhead Gasket - Pre-Installed on 

Rear of Panel

Mounting 

Bracket

2-1/8” (55mm) 

Hole

Spacing Nut (x2)

Clamping Nut (x2)

Lock    

Washer (x2)

GENERATOR METER

VAAFH AC/DC

MODEL: 091-247

3 YEAR WARRANTY

INSTRUCTION MANUAL

File: VAAFH_12-10_081015.indd

Rev: 2

Revised By: SO

Date: 08-10-2015

170 Cherry Avenue

West Sayville, NY 11796

www.kussmaul.com

Ph: 800-346-0857

Fax: 631-567-5826

[email protected]

1

Summary of Contents for 091-247

Page 1: ...he display can be remotely turned ON OFF All set up calibration and alarm values are saved to non volatile memory The system is complete with DC amp shunt voltage and current transformers and is facto...

Page 2: ...e at source To AC distribution panel 2 2 5 max 3 max CT 1 CT 1 CT 1 CT 2 CT 2 DC DC 5 VDC alarm N U VAC VAC L 1 L 1 Tie wrap wire hold down point White Orange Black Red Orange White DC Interface box L...

Page 3: ...AWG cable Wire colors used are black and red One end will have factory terminated QD s which can be connected to the Interface box see wiring diagram The opposite end must be terminated with ring lug...

Page 4: ...fter 60 seconds from the last key press For each menu or sub menu item the following is true Pressing the q or p keys moves highlighted selection down or up Pressing the QUIT key returns you to the Ma...

Page 5: ...d reading then press the accept button when done ATTENTION Calibration should only be performed by qualified personnel Published accuracies are based on proper calibration in conjunction with the 773...

Page 6: ...is ever forgotten the instrument can be reset back to factory default see Reset to Default Caution Resetting to factory default will reset all alarm and calibration settings as well B Zero Generator...

Page 7: ...system and causes the Main Page to be displayed SPECIFICATIONS Power Supply 9 50 to 33 00 VDC 100mA Operating Temperature 32 to 122 F 0 to 50 C Size 4 3 x 4 3 x 3 5 deep 110 x 110 x 89 mm Display Dat...

Reviews: