03
®
II. CENELEC DIRECTIVES :
The instruments conform to CENELEC Low-voltage directive
2014/35/EC, Electromagnetic compatibility directive 2014/30/EU &
RoHS directive 2011/65/EU.
Measurement Category
Measurement Category IV
is applicable to test & measuring circuits
connected at the source of the building’s low-voltage MAINS
installation. Examples are measurements on devices installed before
the main fuse or circuit breaker in the building installation.
Measurement Category III
is applicable to test & measuring circuits
connected to the distribution part of the building’s low-voltage MAINS
installation. Examples are measurements on distribution boards
(including secondary meters), circuit-breakers, wiring, including
cables, bus-bars, junction boxes, switches, socket-outlets in the fixed
installation, & equipment for industrial use & some other equipment
such as stationary motors with permanent connection to the
fixed installation
Measurement Category II
is applicable to test & measuring circuits
connected directly to utilization points (socket outlets & similar points)
of the low-voltage MAINS installation. Examples are measurements
on MAINS CIRCUITS of household appliances, portable tools &
similar equipment.
04
®
IV. GENERAL SPECIFICATIONS :
Display :
3-5/6 digits 6,000 counts
Polarity :
Automatic
Update Rate :
5 per second nominal
61 Segments Bar graph :
40 per second max
Operating Temperature :
-10°C to 50°C
Relative Humidity :
Maximum relative humidity 90% for temperat-
ure up to 28°C decreasing linearly to 50% relative humidity at 50°C
Pollution Degree :
2
IP Rating :
IP40
Storage Temperature :
-20°C to 60°C, < 80% R.H. (with battery
removed)
Altitude :
Operating below 2000m
Temperature Coefficient :
nominal 0.1 x (specified accuracy) /
°C @(-10°C ~ 18°C or 28°C ~ 50C), or otherwise specified
Sensing :
AC, True RMS
Safety :
ETL certified per IEC/UL/EN61010-1 Ed. 3.0,
IEC/UL/EN61010-2-030 Ed. 1.0, IEC/UL/EN61010-2-033 Ed. 1.0,
IEC/UL/EN61010-031 Ed. 1.1 and the corresponding CAN
/CSA-C22.2 regulations to Measurement Categories:
CAT III 1000 V AC & DC and Category IV 600V AC & DC
Compliance to IEC/EN61557:
IEC/EN61557-1 Ed. 2.0, IEC/EN61557-2 Ed. 2.0 &
IEC/EN61557-10 Ed. 2.0
(Tested per CE requirements, not covered by ETL certification)
Overload Protections :
Insulation Resistance,
μ
A & mA: 0.4A/1KV, IR 30kA,
F Fuse; or better
A: 11A/1KV, IR 20kA, F Fuse; or better
V: 1100Vrms
mV, & Others: 1000 Vrms
Transient Protection :
8kV (1.2/50s surge)
E.M.C.:
Meets EN61326-1:2013
In an RF field of 3V/m:
Total Accuracy = Specified Ac 25 digits
Performance above 3V/m is not specified