21 / 44
5.3 Exchanging Data cyclically
To configure the gateway component, you have to perform the
appropriate settings with the configuration software of your
PROFINET -Controller.
The gateway component is equipped with virtual slots (installation
positions). PROFINET controllers use these slots to address selected
process data. Each slot contains one module. You can assign process
data to these modules that are to be exchanged.
Slot
Module
Id
Offset
0
DAP
0x80050000
--
1
Input 16
0x00000005
Output Off 0
2
Input 16
0x00000005
Output Off 16
3
Input 32
0x00000006
Output Off 32
4
Input 32
0x00000006
Output Off 64
5
Input 32
0x00000006
Output Off 96
6
Input 64
0x00000007
Output Off 128
7
Input 64
0x00000007
Output Off 192
8
Input 64
0x00000007
Output Off 256
9
Output 16
0x00000050
Input Off 0
10
Output 16
0x00000050
Input Off 16
11
Output 32
0x00000060
Input Off 32
12
Output 32
0x00000060
Input Off 64
13
Output 32
0x00000060
Input Off 96
14
Output 64
0x00000070
Input Off 128
15
Output 64
0x00000070
Input Off 192
16
Output 64
0x00000070
Input Off 256
Info!
The gateway component supports only a submodule with data
per module.
Configuration