Gateway Component for PROFINET
15 / 44
4.2 Requirements
The Gateway was designed for use in a control cabinet.
ü
The protection class of the control cabinet must be equivalent to at least
IP54.
ü
For installation in the control cabinet you need a DIN rail 35 x 7.5 mm
(EN50022).
◦ Install the DIN rail horizontally in the control cabinet according to
the manufacturers' specifications. When doing so, make sure that
the Gateway is at a sufficient distance from other devices.
NOTICE
Your gateway could be damaged if temperatures are too high.
è
Make sure that the ambient temperature in the control cabinet is less
than 60 °C.
è
Keep the ventilation slots unobstructed. These must not be covered by
cables etc.
è
Maintain sufficient distance from other devices.
Illustration 5:
Distances for installation
◦ Connect each gateway component individually to functional earth.
When doing so, make sure that the power supplies of both
gateway components have the same ground.
ð
Your control cabinet now meets all requirements for installing the
gateway.
Installation