
11
a.
Provide a passive air supply to the home. The air vent should be a minimum of 4” in
diameter.
b.
The air supply must be provided to the same room that the stove is installed in.
c.
The air supply should utilize a barometric damper so that air is only supplied to the room
if the house pressure becomes negative.
Visit
www.woodheat.org
for more information on the use of outside air.
PLEASE REFER TO SECTION 4-
Wood Burning Operation Instructions
before lighting your first fire.
Section
3.2
–Residential Insert Installation
You must have 18” of hearth extending beyond the face of the stove. Since many fireplace hearths are 18”
from the face of the opening, you may need to add a hearth extension to achieve proper clearance. Please
refer to Section 6 for complete clearance diagram.
With the addition of a fireplace insert surround kit (part #KA-SEQSURR) your Sequoia unit may be
installed and used in masonry fireplaces only (lined, masonry chimneys constructed in accordance with
NFPA 211 guidelines).
NOT APPROVED FOR USE IN FACTORY–BUILT OR ZERO
CLEARANCE FIREPLACES.
If your masonry chimney is damaged, deteriorated, or unlined, a stainless steel liner (8” diameter)
with thermal wrap will need to be installed and connected directly to the Sequoia insert flue opening. If
you are unsure of the condition of your chimney, have it cleaned and inspected by your dealer or a chimney
professional. Use and install liner kits that are approved to UL 1777 only.
Tools and materials Required
1.
7/16” wrench
2.
Flat blade screwdriver
3.
KA-SEQSURR Fireplace surround kit.
4.
Bricks or a metal roller to level stove in fireplace (you may use the leveling bolts provided in
the fireplace surround kit for most applications.)
5.
Unfaced fiberglass insulation
6.
Small rug or utility blanket
Prior to installation:
1.
Check for cracks, loose or damaged mortar joints, blockages, or extraordinary deterioration.
2.
The chimney must have at least a 2” clearance to combustible inside and outside the house.
3.
The chimney must have a 5/8” thick fireclay liner. If you have an older, unlined masonry
chimney, then you must install an approved chimney liner system including a thermal wrap that
will bring your existing chimney up to the requirements of U.L. 1777. Contact your dealer or a
licensed chimney professional if you have any questions.
4.
Check for any gap existing between the masonry fireplace construction and the fascia masonry. If
there is a gap, seal with a high temperature masonry mortar.
5.
If outside air is required by local building code then it should be connected to the back of the
fireplace prior to installation.
a.
The outside air vent can not exceed in length, the vertical height of the exhaust flue
b.
The outside air vent must be installed where it will remain free of snow, ice, or debris.
c.
The outside air vent must not terminate close to exhaust vents.