7. 

General displays 

The two upper rows of the LEDs provide important information on the operating processes and error mes-
sages. The displays described below are intended as standard. 

 

7.1. 

Monitoring on 

Using this green LED (after the genset start-up), the release of the operating-dependent delayed alarms is 
signalled. As soon as the motor has started up, this LED flashes until the monitoring is released. The display 
goes out at the beginning of the shut-down process. 

7.2. 

Automatic system locked 

The display is switched on by a signal on the Q

UICK 

S

TOP INPUT 

(E

MERGENCY 

S

TOP

), or together with such 

alarms that lead to the shut-down of the genset. This LED indicates that the automatic system is locked for 
further start attempts and thus genset operation is inhibited. 
The automatic system is unlocked by selecting the O

FF

operating mode (after eliminating the cause of the er-

ror). To do so, any actuated external emergency stop buttons must also be unlocked. 

7.3. 

Start control 

The message will be activated as soon as a start request is present in 

AUTOMATIC 

mode or if 

MANUAL

 or 

TEST 

mode has been selected. The display flashes as long as there is no start release. The display goes out as 
soon as the genset exceeds the ignition speed during start-up (recognised from the D+ signal of the genera-
tor and also from the speed sensor signal according to the parameterisation). Switching on the starter is then 
inhibited, even if attempted manually. 

7.4. 

Failed start / Motor malfunctions 

This alarm is controlled by three criteria. That's why this message has expired needs to be interpreted. The 
message is controlled if  

  the genset has not started at the end of the starting program. This message, 

FAILED START

, is displayed 

with a continuous light (without flashing). The automatic system is inhibited. 

  The automatic system is already running and is brought to a standstill without a stop command. This 

message, 

SPEED MEASUREMENT FAILED

, is indicated with a flashing light and the automatic system is inhib-

ited. 

the genset continues to run after the stop time has expired. This message, M

OTOR DOES NOT SHUT DOWN

 

flashes, the automatic system is not locked. 

8. 

Operating modes 

8.1. 

Off operating mode 

The O

FF 

position is automatically selected (reset function) during the application of battery voltage in order to 

prevent the triggering of an unintentional start-up. When switching to O

FF 

from another operating mode: 

  a genset operation is immediately ended. 

  previously displayed error messages, except the fault messages 9 and 10, are cleared as long as their 

alarm contact is still active. 

  the automatic system is unlocked. However, if the Q

UICK 

S

TOP 

(E

MERGENCY 

S

TOP

)

 

input is still active, un-

locking is not possible; the 

AUTOMATIC SYSTEM LOCKED

 message remains. 

  Manual operating mode 

The 

START CONTROL

 indication flashes as long as there is no start release and the 

SWITCH ON AUXILIARY 

DRIVES

 signal is present. If no auxiliary drives are required (for start release), terminal 8 from X2, 

START 

RELEASE

 should be switched with L-. The motor can be started using the S

TART

 key.  

In order to switch off the genset, the O

FF 

or (in the event of the external start command being missing) 

A

UTOMATIC 

operating mode must be selected. 

8.2. 

Auto operating mode 

After the external start command is present the genset will be started after the parameterised delay time has 
elapsed. The 

START CONTROL

 indication flashes as long as there is no start release and the 

SWITCH ON 

Summary of Contents for KEA 293 PST

Page 1: ...All functions allocated to the genset are included for sprinkler operation Ten displays can be selected as alarms or operational indicators Provision has been made for remote acknowledgement of alarms...

Page 2: ...5 8 3 Test operating mode 6 8 4 Sprinkler operation 6 9 Error messages Programmable operation indicators 6 9 1 Use as an operational indicator 6 9 2 Use as an error message 6 9 3 Alarms 9 and 10 6 9 4...

Page 3: ...unit The connection regulations must be observed 3 The installation and commissioning must only be carried out by sufficiently qualified personnel 4 Applicable regulations especially those of the VDE...

Page 4: ...can be selected using the keys 6 2 Start key The motor can be started in MANUALoperating mode by actuating this button If the motor needs to be pre heated the pre heating device must be externally co...

Page 5: ...m is controlled by three criteria That s why this message has expired needs to be interpreted The message is controlled if the genset has not started at the end of the starting program This message FA...

Page 6: ...t is free Stopping can then be carried out via the OFF operating mode or always via Emergency Stop 9 Error messages Programmable operation indicators Any of the 10 LEDs can either display an error mes...

Page 7: ...et is immediately ready for operation in the event of a start request sprinkler request 10 Remote acknowledgement Existing alarms can be remotely acknowledged with a signal L on terminal 32 A constant...

Page 8: ...kler operation run on time 0 sec Stop time 30 sec 13 2 Start process gas engine Starter on If the starter speed is exceeded the switching on of the ignition is delayed e g after 2 sec Then another 2 s...

Page 9: ...70 C Operation 10 C 50 C Standards regulations DIN VDE 0160 14 2 Auxiliary voltage Switchable 9 12 15V or 14 24 35V DC 14 3 Analogue input Battery voltage monitor 14 4 Digital inputs and outputs Input...

Page 10: ...293 PST_EN_Ver 2016 07 01 doc 10 Alfred Kuhse GmbH Telephone 49 4171 798 0 E mail kuhse kuhse de Subject to technical changes An der Kleinbahn 39 21423 Winsen Fax 49 0 4171 798 117 http www kuhse de 1...

Page 11: ...ST_EN_Ver 2016 07 01 doc 11 Alfred Kuhse GmbH Telephone 49 0 4171 798 0 E mail kuhse kuhse de Subject to technical changes An der Kleinbahn 39 21423 Winsen Fax 49 0 4171 798 117 http www kuhse de 15 2...

Page 12: ...Operating instructions KEA 293 PST 12 12 File BA_KEA 293 PST_EN_Ver 2016 07 01 doc 16 Drilling template Scale 1 1 print without scaling...

Reviews: