O
PERATION
M
ODES
112-MOBL-3
In the case of a
Remote start command with generator operation,
the genset is started and switches the
generator CB on.
The
Start without generator operation
can be used, for example, to supply more delicate consumers. If, for
example, the generator power is sudden needed, the genset can be started up via this input. The genset starts
but don't take the load. If a remote start command now occurs, the system is able to switch immediately to
generator supply.
O
PERATION MODE
T
EST
The auxiliary drives are switched on when the system is switched to T
EST MODE
. The start sequence begins
when the start is enabled. The generator CB is switched on by pressing the G
EN
.
ON
(
I
) or switched off or by
G
EN OFF
(
O
).
The generator is switched on if a R
EMOTE START WITH GENERATOR OPERATION
command is applied. It is in
this case not possible to switch off the generator CB manually.
Select operation mode O
FF
to shutdown the genset or A
UTO
if there is no automatic start.
S
PRINKLER
O
PERATION
The following functions are provided for operation of an electric sprinkler pump:
−
Set all alarms as warning ones,
−
Start sequence with 10 (can be set by customer) start attempts,
−
For the run-up of the sprinkler pump: break or no break for the normal consumers,
−
You can select when the sprinkler is no longer required, if the Sprinkler operation is
cancelled after the C
OOLING DOWN
P
ERIOD AFTER
SPRINKLER or
is manually switched off.
The time stage for the C
OOLING DOWN
P
ERIOD AFTER
SPRINKLER
CAN
be set from 10 to 2400 seconds.
The sprinkler operation is not terminated automatically but must be ended manually if this stage is set to 0
seconds.
If this is the case, the O
FF
mode indicator flashes.
The genset can now only be stopped via I
MMEDIATE
S
TOP
or the mode O
FF
.
The break duration of the normal consumers for the run-up of the sprinkler pump can be set from 0 to
24 seconds. The emergency consumers are not switched off if it is set to 0 sec.
The consumers are switched to generator supply if during the sprinkler operation a R
EMOTE START WITH
GENERATOR OPERATION
occurs. The normal consumers are switched off after expiry of the C
OMMAND
-
OFF
DELAY
when the remote start command is cancelled.
The sprinkler mode prevents that the genset is switched off or shutdown due to an alarm. If a shutdown
alarm is triggered, however, the common alarm
SHUTDOWN
is issued.
D
OCUMENT
H
ISTORY OF
O
PERATION MODES
Revision Modification Released
Revision Modification Released
06-01-11 First
edition
05-12-02
06-11-25 Format
06-11-25
Manual
voltage
control
Operation Modes 112- MOBL-3 / 07-01-25