Manual - analog (U/I)
Sendix M3661 / M3681
Sendix M3661R
Sendix M5861
ENG - 8 (R60722.0002 - Index 3)
3.2 LED combinations for scaling
Display
LED
Meaning
Error cause
Addition
Green LED flashes 1x
•
1x
Activation of scaling
input 1 detected and
confirmed.
Green LED flashes 3x
•
3x
Activation of scaling
input 2 detected. The
new measuring range
has been taken over.
Red LED flashes 3x
•
3x
Error during the scaling
process. The new
measuring range has
not been taken over.
Selected measuring
range < 22.5° or
> 65536 rev.
Scale another measu-
ring range.
Green/red/green
sequence
•
•
•
1x 1x 1x
Reset of the scaled
measuring range.
Default measuring
range is loaded. Preset
is performed at the
current position.
4. Standard function
As a standard, the corresponding desired output signal ( 4 … 20m A / 0 … 10 V /0 … 5 V) is linearily factory-scaled over 16 revo-
lutions and supplied in the CW or CCW direction of rotation according to customer requirement.
The reference point is indicated by the LED from 0 … 1°.
cw variant
ccw variant
Roll-
over
Reference display (LED)
0°
16 revol.
version 0 ... 5 V
vers
ion 4 ... 20
mA
version
0 ... 10
V
20 mA / 10 V
5 V
4 mA
0 mA / 0 V
0°
16 revol.
Roll-
over
version 0 ... 5 V
version 4 ... 20 mA
version 0 ... 10 V
20 mA / 10 V
5 V
4 mA
0 mA / 0 V
Reference display (LED)