2.2 Mounting in a control panel
Mount the device away from heat
sources and avoid direct contact with
corrosive liquids, hot steam or similar.
Provide a free space of 10 mm all
around the device for its ventilation.
The device should be mounted so that
the terminals are out of the reach of
the operator and cannot be touched
by him. When mounting the device,
consider the fact that only the front
side is classified as accessible for the
operator.
Mounting instructions
1. Remove the mounting clip from the device.
2. Insert the device from the front into the panel
cut-out, ensuring the front-panel gasket is
correctly seated.
3. Slide the fixing clip from the rear onto the
housing, until the spring clamps are under
tension and the upper and lower latching lugs
have snapped into place.
Note: In case of proper installation, IP65 can be
reached on the front side.
2.3 Electrical Installation
The device must be disconnected
from any power supply prior to any
installation or maintenance work.
Make sure that no more voltages
LIABLE TO CAUSE AN ELECTRO-
CUTION are present.
AC-powered devices must only be
connected to the low-voltage net-
work via a switch or circuit breaker
installed close to the device and
marked as their disconnecting device.
Installation or maintenance work
must only be carried out by qualified
personnel and in compliance with the
applicable national and international
standards.
Take care to separate all extra-low
voltages entering or exiting the device
from hazardous electrical conductors
by means of a double or reinforced
insulation (SELV circuits).
The device must be protected
externally for its proper operation.
Information about the prescribed
fuses can be found in the technical
information.
• During installation, make sure that the supply
voltage and the wiring of the output contacts
are both fed from the same mains phase, in
order not to exceed the maximum permitted
voltage of 250V.
• The cables and their insulation must be
designed for the planned temperature and
voltage ranges. Regarding the type of the
cables, adhere to the applicable standards of
the country and of the plant. The cross sections
allowed for the screw terminals can be found in
the technical data.
• Before starting the device, check the cables
for proper wiring and tightening. The screws of
unused screw terminals must be screwed to the
stop, so that they cannot loosen and get lost.
• The device has been designed for overvoltage
category II. If higher transient voltages cannot
be excluded, additional protection measures
must be taken in order to limit the overvoltage
to the values of CAT II.
Advice on noise immunity
All connections are protected against external
sources of interference. The installation location
should be chosen so that inductive or capacitive
interference does not affect the device or its con-
necting lines! Interference (e.g. from switch-mode
power supplies, motors, clocked controllers or
contactors) can be reduced by means of appro-
priate cable routing and wiring.
Measures to be taken:
Use only shielded cable and control lines.
Connect shield at both ends. The conductor
cross-section of the cables should be a minimum
of 0.14 mm
2
.
The shield connection to the equipotential bonding
should be as short as possible and with a contact
area as large as possible (low-impedance).
Only connect the shields to the control panel, if
the latter is also earthed.
Install the device as far away as possible from
noise-containing cables.
Avoid routing signal or control cables parallel to
power lines.
2
!
DANGER
!
DANGER
!
CAUTION