Installation and Operation Manual 23
7.4.4
Working parameters
Interface
Description
-- RUN SETTING--
→1: VPV-START
2: DELAY-START
3: VAC-MIN
Press UP/DOWN button to move
corresponding options, press ENTER to
enter into the selected menu; return back
setup interface (refer to 7.4) by pressing
ESC, there are 6 options in total, including
VPV-START,DELAY-START ,VAC-MIN ,V
AC-MAX , FAC-MIN, FAC-MAX, ACTIVE
POWER, REACT POWER, FREQ POWER
and V LOAD.
7.4.4.1 Starting-up voltage
Interface
Description
---START-UP VOLT---
INPUT:
350V
UNIT:
V
Press UP/DOWN to increase or
decrease the input figure, move the
cursor
backwards
and
confirm
completion of input as well as enter into
interface of please restart (refer to
7.4.4.11) by pressing ENTER button,
press ESC to move the cursor frontward
and return back working interface (refer to
7.4.4); the input figure is between 350 and
850, default is 350.
7.4.4.2 Starting-up delay time
Interface
Description
-- START-UP DELAY--
INPUT:
60
UNIT:
SEC
Press UP/DOWN to increase or
decrease the input figure, confirm input
and enter into interface of please restart
(refer to 7.4.4.11) by pressing ENTER
button; press ESC to 4 cancel input and
return back working interface (refer to
7.4.4), input figure is between 60 and 300.
This parameter is changed by grid standards.