7.8
Alerts and warnings – overview
Alert
Description
Sens. fail. discharge
Failure pressure transmitter
discharge side (value under 4
mA). Replace PT and reset
system.
System pressure too
low
System pressure too long under
minimum value (3--5--13).
System pressure too
high
System pressure too long above
maximum value (3--5--11).
No water available
Insufficient water or pressure at
suction side.
Thermal failure
Thermal failure urgent.
Therm. supply valve
Thermal failure supply (current
too high).
Level sensor fail.
Failure level sensor in receiver
tank (value under 4 mA). Replace
l.s. and reset system.
Fire alarm
Alert when opening the ”external
ON” contactor
Warning
Description
Maintenance required
Customer service required.
Therm. fail Pump 1
Thermal failure pump 1 (motor
current too high).
Therm. fail Pump 2
Thermal failure pump 2 (motor
current too high).
Therm. fail Pump 3
Thermal failure pump 3 (motor
current too high).
Therm. fail Pump 4
Thermal failure pump 4 (motor
current too high).
Therm. fail Pump 5
Thermal failure pump 5 (motor
current too high).
Therm. fail Pump 6
Thermal failure pump 6 (motor
current too high).
Pump 1 out of service
1. Pump set to manual OFF.
Deactivate by selecting automatic
mode.
Pump 2 out of service
2. Pump set to manual OFF.
Deactivate by selecting automatic
mode.
Pump 3 out of service
3. Pump set to manual OFF.
Deactivate by selecting automatic
mode.
Pump 4 out of service
4. Pump set to manual OFF.
Deactivate by selecting automatic
mode.
Pump 5 out of service
5. Pump set to manual OFF.
Deactivate by selecting automatic
mode.
Pump 6 out of service
6. Pump set to manual OFF.
Deactivate by selecting automatic
mode.
High water level
Water level in receiver tank too
high.
Critical water level
Water level in receiver tank critical
(almost empty).
Water level too low
Water level in receiver tank too
low (system shut down for dry
running protection).
24 V out of range
Internal 24 V outside of the valid
range.
Anal. 5 V out of range
Internal 5 V outside of the valid
range.
3 V out of range
Internal 3 V outside of the valid
range.
External OFF
Warning when opening the
”external OFF” contactor