5 Installation at Site
33 of 76
EtaLine Pro
1168.87/01-EN
5.7.3.5 Connection to power supply network and motor
DANGER
Touching or removing terminals
Danger to life from electric shock!
▷
Never open or touch terminals or plug-type connections until the pump set has
been de-energised.
Fig. 17:
Preparing the power cable
1. Prepare the power cable for connection. (
11
Fig. 18:
Connecting the power cable
2. Route the power cable for the power supply network through the cable gland
and connect the cable to the specified terminals.
3.
For connection to IT mains only:
Disconnect the filter capacitors in the mains
input from the protective conductor by removing the three red jumpers.
NOTE
IP55 enclosure protection as specified in the technical data is only provided if the
cover has been fitted properly.