KSB Compacta Supplementary Operating Manual Download Page 10

3 Replacing the LevelControl Basic 2 BC Control Unit

10 of 12

Compacta / mini-Compacta

Setting the inlet nozzle level

Table 5: 

Control unit: Navigation keys

Key

Description

Arrow keys (up/down):

Move up/down in the menu options.

Increase/decrease a numerical value

Esc

Escape key:

Cancel entry without saving it.

When entering numbers: Go to the previous digit.

Move up one menu level.

OK

OK key:

Confirm entries.

Confirm a menu selection.

When entering numbers: Go to the next digit.

1.

Press the "ESC" and "OK" keys simultaneously: P3.1.2.1 is displayed.

2.

Press "Up" key: P3.1.2.2 is displayed.

3.

Press "OK".

4.

Select the 

lowest

 inlet nozzle used from the table below and look up the

relevant setting (e.g. 1 for inlet nozzle level 180 mm). Then make the appropriate
setting (e.g. 1) at the control unit, using the "Up" and "Down" keys.

5.

To confirm the selected value press "OK".

6.

Press "ESC" to exit parameterisation.

Table 6: 

Setting the inlet nozzle level

Inlet
[mm]

Setting

180

1

250

2

320

3

700

4

Vertical

5

Summary of Contents for Compacta

Page 1: ...Floodable Sewage Lifting Unit Compacta mini Compacta Replacing the Control Unit LevelControl Basic 2 BC Supplementary Operating Manual...

Page 2: ...e contents provided herein must neither be distributed copied reproduced edited or processed for any other purpose nor otherwise transmitted published or made available to a third party without the ma...

Page 3: ...General 5 2 3 Intended use 5 2 4 Personnel qualification and training 6 2 5 Consequences and risks caused by non compliance with these operating instructions 6 2 6 Safety awareness 6 2 7 Safety inform...

Page 4: ...control unit 1 2 Target group This supplementary operating manual is aimed at the target group of trained and qualified specialist technical personnel 1 3 Other applicable documents The other applicab...

Page 5: ...aintenance instructions that must be observed to ensure safe operation and prevent personal injury and damage to property are given in the installation operating manual The safety information in all s...

Page 6: ...information contained in this manual and the intended use the following safety regulations shall be complied with Accident prevention health and safety regulations Explosion protection regulations Saf...

Page 7: ...ate the lifting unit outside the limits stated in the data sheet and in the lifting unit s installation operating manual The warranty relating to the operating reliability and safety of the lifting un...

Page 8: ...re that the lifting unit cannot be inadvertently started 2 Open the control unit cover and make sure the control unit is de energised 3 Disconnect the rechargeable battery 4 Clearly mark all conductor...

Page 9: ...e table shown below e g 39 for UZ10 450 D and make the appropriate setting e g 39 using the Up and Down keys of the control unit 5 To confirm press OK 6 Press ESC to exit parameterisation Table 4 Sett...

Page 10: ...Confirm entries Confirm a menu selection When entering numbers Go to the next digit 1 Press the ESC and OK keys simultaneously P3 1 2 1 is displayed 2 Press Up key P3 1 2 2 is displayed 3 Press OK 4...

Page 11: ......

Page 12: ...KSB SE Co KGaA Johann Klein Stra e 9 67227 Frankenthal Germany Tel 49 6233 86 0 www ksb com 2317 8003 02 EN...

Reviews: