Ecowatt
®
Drive K120 series
Product overview
-6-
2.
Check whether the ambient temperature of the VFD in actual use is lower than
-10°C. If yes, use heating facilities.
Note:
For the cabinet VFD, the ambient temperature means the air temperature
inside the cabinet.
3.
Check whether the altitude of the VFD in actual use exceeds 1000m. If it exceeds
1000m, derate 1% for every increase of 100m. When the altitude exceeds 3000m,
consult the local Kruger dealer or office for details.
4.
Check whether the humidity of the actual usage site exceeds 90% and
condensation occurs. If yes, take additional protective measures.
5.
Check whether the actual use site may be exposed to direct sunlight or may have
the chance of ingress of foreign objects. If yes, take additional protective
measures.
6.
Check whether there is dust, explosive gas, or flammable gas in the actual use
site. If yes, take additional protective measures.
2.1.4
Installation confirmation
Check the following after the VFD installation:
1.
Check whether the load ranges of the input power cable and motor cable meet
the actual load requirement.
2.
Check whether correct accessories are selected for the VFD, the accessories are
correctly and properly installed, and the installation cables meet the
requirements of all components (including the reactor, input filter, output reactor,
output filter, DC reactor, braking unit and braking resistor).
3.
Check whether the VFD is installed on non-flammable materials and the
heat-radiating accessories (such as the reactor and braking resistors) are away
from flammable materials.
4.
Check whether all control cables and power cables are run separately and the
routing complies with EMC requirement.
5.
Check whether all grounding systems are properly grounded according to the
requirements of the VFD.
6.
Check whether all the installation clearances of the VFD meet the requirements
in the operation manual.
7.
Check whether the installation conforms to the instructions in the operation
manual. It is recommended that the VFD be installed uprightly.
8.
Check whether the external connection terminals of the VFD are tightly fastened
and the torque is appropriate.
9.
Check whether there are screws, cables, or other conductive items left in the VFD.
If yes, get them out.