3.5 Connection of the room temperature corrector KT-1 and KT-2
Spatial corrector KT-1(2) is connected according to the circuit diagram below. Care should be taken to
correctly connect the UTP cable with the connector RJ-45.
KT - 1
KT - 1
KT - 1
KT - 1
KT - 1
KT - 1
RQ1
RQ2
TEX
TE2
TS
WM
1..
. ..
.8
KT - 1
A+ B- GND +12V
1 2 3 4 5 6 7 8
RJ-45
UTP
RJ-45
P
PLC
A+ B- GND +12V
A+ B- GND +12V
A+ B- GND +12V
A+ B- GND +12V
A+ B- GND +12V
A+ B- GND +12V
S
ELEMENTS CONNECTING
CLIPS
MARK CHARACTERISTICS
KT-1(2)
Room temperature corrector KT-1(2) (optional)
A +
Communication
B -
GND
Power supply
+12 V
PLC
Process module
RQ1
ALARM voltage-free contact
RQ2
RESET voltage-free contact
WM
Communication with Web module
TEX
MODBUS communication with the control system of
the building (BMS)
TS
Communication with the room corrector
TE2
Communication with the basic module MD1
UTP
UTP cable
RJ-45
Connector RJ-45
P
Parallel connection
S
Sequential connection