background image

GB-7

D

GB

F

NL

I

E

 

As not all the effects caused by the equipment 

are known, setting the burner using the pressure 
values is only approximate. It is possible to set 
the burner precisely by measuring the flow rates 
or flue gas.

Restrictors

 

The air volume required for the low-fire rate at a 

given air pressure is determined by the ignition 
position of a butterfly valve, a bypass hole in the 
air valve or an external bypass with restrictor.

Hot-air compensation

 

The combustion air pressure 

p

Air

 must be in-

creased in hot-air operating mode (lambda = 
constant).

0

100

200

300

400

100

150

200

250

T

Air

 [°C]

p

Ai

r

 [%]

 

The gas pressure is increased by 5 – 10 mbar.

 

The total burner capacity 

P

B

 rises as the air tem-

perature 

T

Air

 increases.

0

100

200

300

400

100

110

120

T

Air

 [°C]

P

B

 [%]

Setting the air pressure for low fire and high 

fire
  

 Shut off the gas and air supply.

 

Air measuring nipple 

L

, external dia. = 9 mm (0.35").

p

atm.

p

air

0

L

Loosen the 
screw 2 
turns.

     Fully open 
the air supply.

p

atm.

p

air

0

L

Low fire:

 

The burner must only be ignited at low fire (be-

tween 10 and 30% of the rated capacity Q

max

 – 

see type label).

  • 

 Reduce the air supply on the air control valve 

and set the desired low-fire rate, e.g. using a 
limit switch or mechanical stop.

 

On air control valves with bypass, the bypass 
orifice should be determined on the basis of the 
required flow rate and the existing supply pres-
sure if required.

High fire:

  • 

  Set the required air pressure p

air

 on the air restric-

tor upstream of the burner.

  • 

 When using air restricting orifices: check the air 

pressure p

air

.

Preparing the gas pressure measurement for 

low fire and high fire

  • 

 Connect all measuring devices for subsequent 

fine adjustment of the burner.

 

Leave the gas supply closed.

 

Gas measuring nipple 

G

, external dia. = 9 mm 

(0.35").

  • 

 Read off the gas pressure p

gas

 for the required 

flow rate from the enclosed flow rate curve for 
cold air.

[mbar ("WC)]

[m

3

/h (ft

3

/h)]

p

gas

p

air

p

air

p

gas

Q

air

Q

gas

p

atm

 = 

atmospheric 
pressure.

Summary of Contents for ZIO 165

Page 1: ...Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Changes to edition 11 11 The following chapters have been changed Checking the usage Installation Preparing commissioning Technical data Logistics Declaration of Incorporation Operating instructions D GB GB 1 Translation from the German 032...

Page 2: ...ternal insulation 165 200 Burner size R H K Normal flame Long soft flame Flat flame B D G M Natural gas Coke oven gas town gas Propane propane butane butane Propane propane butane butane L Ignition lance 50 100 150 200 Burner tube length mm 35 135 235 Position of burner head mm 1 to 199 1E to 199E Burner head identifier High temperature version A to Z Construction stage Z Special version Part desi...

Page 3: ...rning in an open combustion chamber Control High Low High Low Off continuous Type of burner head H Max capacity approx 80 depending on the outlet diameter of the burner quarl Medium to high flow velocity Flat flame burner quarl For industrial furnaces and kilns and for burning in an open combustion chamber Control High Low High Low Off continuous limited control range Type of burner head K Capacit...

Page 4: ... units to prevent mechanical stress or transmission of vibration Ensure that the seals are undamaged DANGER Risk of explosion Ensure the connection is gas tight For connecting to ANSI NPT connections An adapter set is required for connection to ANSI NPT see page 12 Accessories Type Gas connection GA Air connection LA ZIO 165 1 11 5 NPT 4 57 ZIO 200 2 11 5 NPT 6 72 Flange hole diameter Weld flange ...

Page 5: ...ion cable see automatic burner control unit operating instructions Connect the ionization electrode to the automatic burner control unit via the ionization cable Ignition electrode Z Length of ignition cable max 5 m 15 ft recom mended 1 m 40 For permanent ignition max ignition cable length 1 m 40 Lay the ignition cable individually and not in a metal conduit Install the ignition cable separately f...

Page 6: ...st volume into the furnace chamber Determining the flow rates QGas PB Hu QLuft QGas λ Lmin QGas Gas flow rate in m3 h ft3 h PB Burner capacity in kW BTU h Hu Gas calorific value in kWh m3 BTU ft3 QLuft Air flow rate in m3 n h scfh λ Lambda air index Lmin Minimum air requirement in m3 n m3 n scf scf Use the lower calorific value Hu Information on the gas quality supplied can be obtained from the co...

Page 7: ...xternaldia 9mm 0 35 patm pair 0 3 5 2 4 L Loosen the screw 2 turns Fully open the air supply patm pair 0 5 Low fire The burner must only be ignited at low fire be tween 10 and 30 of the rated capacity Qmax see type label Reduce the air supply on the air control valve and set the desired low fire rate e g using a limit switch or mechanical stop On air control valves with bypass the bypass orifice s...

Page 8: ...n adjustable gas restrictor be installed upstream of the burner open the restrictor by approx a quarter Open the gas supply Ignite the burner The safety time of the automatic burner control unit starts to elapse If no flame forms check and adjust the gas and air pressures of the start gas adjustment In the case of operation with bypass e g when using an air gas ratio control check the bypass nozzl...

Page 9: ... Cooling air While the burner is switched off and depending on the furnace temperature there must be a cer tain air flow for cooling the burner components 700 800 900 1000 1100 1200 1300 1400 0 6 4 2 5 3 1 0 12 8 4 10 6 2 ZIO ZIO KB E ZIO K Furnace temperature C Cooling air at 20 C air volume at rated capacity Cooling air at 450 C air volume at rated capacity Diagram the relative air volume in per...

Page 10: ...ark plug 1 using the dowel pin 2 10 Adjust spark plug and electrode to the measured total length L 11 12 Turning the spark plug makes it easier to feed the electrode into the burner insert Checking the burner 16 13 14 15 If the burner insert is dismantled the gas housing gasket will have to be renewed 17 Place the burner insert in a safe place Depending on the amount of dirt or wear replace the ig...

Page 11: ...t of malfunction DANGER Electric shocks can be fatal Before working on possible live components ensure the unit is discon nected from the power supply Risk of injury Burner heads have sharp edges Fault clearance must only be undertaken by author ized trained personnel If no fault is detected when checking the burner proceed to the automatic burner control unit and check for faults in accordance wi...

Page 12: ...d setting Order number 05012009 Adapter set 8 8 For connecting ZIO to NPT ANSI connections Burner Adapter set Order No ZIO 165 BR 165 NPT 74922636 ZIO 200 BR 200 NPT 74922637 Nozzle set Available on request for connecting integrated ignition lances to NPT threads Technical data Gas supply pressure approx 20 to 50 mbar air supply pressure approx 25 to 40 mbar each depending on flame shape gas type ...

Page 13: ...as Description Burner for gas Typenbezeichnung Type BIO BIOA ZIO BIC BICA ZIC BIOW ZIOW BICW ZICW Anhang I Artikel Annex I Article 1 1 3 1 1 5 1 3 2 1 3 4 1 5 2 1 7 4 Folgende harmonisierte Normen wurden angewandt The following harmonized standards have been applied Lotte Büren Sandra Runde Datum Date Konstrukteurin Designer Sandra Runde ist bevollmächtigt die speziellen technischen Unterlagen gem...

Page 14: ...ns please contact your local branch office agent The addresses are available on the Internet or from Elster GmbH We reserve the right to make technical modifications in the interests of progress info kromschroeder com www kromschroeder com Contact Certification Approval for Russia Certified by Gosstandart under Technical Regulations Approved by Rostekhnadzor RTN ...

Reviews: