Ensure that the O-ring is fitted in the new measur-
ing unit, see Figure

   

.

5

6

14

11

15

13

4

3

8

12

7

9

10

10

    First insert 

the washer 

into the valve 

disc, and then 

the O-ring.

 

Replace the O-rings on the housing and the 
valve seat.

19

24

17

16

18

25

20

21

22

23

  

  Follow the reverse procedure when reassembling 

using the O-rings from the seal set.

  

 We also recommend replacing the sealing rings 

on the pressure test points.

 4 

 Connect the impulse line.

 5 

 Check tightness and function, see page  

(Tightness test) and page  4 (Checking the 
function).

Maintenance

In order to ensure smooth operation:
Check the function and tightness of the JSAV every 
year, or every six months if operated with biologically 
produced methane, see page  4 (Checking the 
function) and page 3 (T
ightness test).

 

In the case of malfunctioning, check the 
measuring unit and valve disc and replace if 
necessary. 
Selecting spare parts: 
see free PartDetective DVD:

  

www.kromschroeder.com 

 Products

 → 

DVD

 

→ 

PartDetective, (D/GB). 

Replacing spare parts: 
see page 5 (Replacing the measuring unit), 
see page 6 (Replacing the valve disc).

 

After carrying out maintenance work or replacing 

spare parts, check for tightness and function, 
see page  3 (Tightness test) and page  4 
(Checking the function).

Technical data

Gas type: natural gas, town gas, LPG (gaseous), 
biologically produced methane (max. 0.02 %-by-
vol. H

2

S) or air. 

The gas must be dry in all temperature conditions 

and must not contain condensate.
Max. inlet pressure p

u

 4 bar (58 psig).

Max. test pressure for testing the JSAV: 
temporarily < 15 min. 6 bar (87 psig).
Max. test pressure for testing the impulse line: 
temporarily < 15 min. 750 bar (10.8 psig).

Trip pressures pre-set at the factory to:

p

do

: 120 mbar, 

p

du

: 10 mbar.

Trip pressure ranges, see page 4 (Replacing 

the spring), Spring table.

Accuracy group: AG 10.
Ambient temperature: 

-15 to +60°C (5 to 140°F).

Connection for housing: 

JSAV..R: Rp internal thread to ISO 7-1, 
JSAV..N: NPT internal thread, 
JSAV..F: PN 16 flange to ISO 7005.

Connection for impulse line: 
DN 8 (NPT 

1

8

).

Housing: AlSi,
diaphragm: NBR, 
valve seat: aluminium, 
valve stem: stainless steel, 
valve disc: steel with vulcanized NBR seal.

Summary of Contents for JSAV 25

Page 1: ...only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM sp...

Page 2: ...com D 49018 Osnabr ck Germany JSAV pu 4 bar pdu 10 mbar 8 16 pdo 140 mbar 10 210 T 20 C 60 C Klasse A IS CE 0085AS0202 www kromschroeder com D 49018 Osnabr ck Germany Installation CAUTION Please obser...

Page 3: ...on nut and compression fitting onto the impulse line On the JSAV T remove the blind plug and con nect an NPT 1 8 impulse line 5 Install the impulse line and seal with approved sealing material Ensure...

Page 4: ...pdo according to the outlet pressure pd of the pressure regulator 20 0 40 60 80 100 140 180 220 260 300 340 50 100 150 200 250 300 350 400 450 500 pd mbar p do mbar VSBV JSAV 2 Remove the breather scr...

Page 5: ...pressures pdo and pdu on the adhesive label s 10 Screw in the breather screw plug 11 Check tightness and function see page 3 Tightness test and page 4 Checking the function Resetting Ensure that the...

Page 6: ...st and page 4 Checking the function Replacing the valve disc The valve disc has to be replaced if the JSAV is leaking We recommend cleaning the O ring seats and lightly greasing the O rings with Kl be...

Page 7: ...c and replace if necessary Selecting spare parts see free PartDetective DVD www kromschroeder com Products DVD PartDetective D GB Replacing spare parts see page 5 Replacing the measuring unit see page...

Page 8: ...d functions must be checked in accordance with the section entitled Maintenance If the product passes the aforementioned function tests you can continue to use it until the next sched uled maintenance...

Reviews: