background image

GB-2

D

GB

F

NL

I

E

Checking the usage

Gas filter GFK is used for filtration of the fuel gas 
and combustion air supply to all gas consuming 
appliances.

This function is only guaranteed when used within the 

specified limits – see page 3 (Technical data). Any 
other use is considered as non-compliant.

Type code

Code

Description

GFK

Gas filter

15 – 50

Nominal size

T

T-product

R
F
N

A

Rp internal thread

Flanged connection to ISO 7005

NPT internal thread

ANSI flange

10

40

60

Max. inlet pressure p

u

 

max

1 bar (14.5 psig)

4 bar (58 psig)
6 bar (87 psig)

-

-6

Screw plug at the inlet 

and outlet

Pressure test point at the inlet 

and outlet

Part designations

GFK..F

GFK..R

1

1

3

2

2

1

  Housing cover

  Lower housing section

  Pressure test point

Type label

 

Max. inlet pressure: see type label.

D-49018 Osnabrück, Germany

GFK 

p

u max

 

Installation

 

CAUTION

Dropping the device can cause permanent dam-
age. In this event, replace the entire device and 
associated modules before use.

 

Installation position: any, in horizontal or verti-
cal pipework – recommended: housing cover 
to the side.

 

The housing must not be in contact with masonry, 

minimum distance 20 mm (0.79").

 

> 20 mm

 

We recommend applying a protective coating 
when installing in the open air.

GFK..R

2

3

1

4

GFK..F

2

3

1

Tightness test

 1 

 To be able to check the tightness, shut off the 

downstream pipeline close to the gas filter.

N

2

 

≤ 

1,2 x p

u max

3

2

 4 

 Tightness OK: open the pipeline.

 

Pipeline leaking: replace the seal.

Summary of Contents for GFK Series

Page 1: ...nstructions as follows DANGER Indicates potentially fatal situations WARNING Indicates possible danger to life and limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Change...

Page 2: ...outlet Part designations GFK F GFK R 1 1 3 2 2 1 Housing cover 2 Lower housing section 3 Pressure test point Type label Max inlet pressure see type label D 49018 Osnabrück Germany GFK pu max Installation CAUTION Dropping the device can cause permanent dam age In this event replace the entire device and associated modules before use Installation position any in horizontal or verti cal pipework reco...

Page 3: ...FK 40 8 GFK 50 8 GFK 65 8 GFK 80 20 GFK 100 20 GFK 125 60 GFK 150 60 GFK 200 80 GFK 250 80 Checking tightness and function When replacing the filter pad the gas filled space in the GFK is opened Therefore check for tight ness once the filter pad has been reinstalled 12 To be able to check the tightness shut off the downstream pipeline close to the gas filter 1 2 x pu max N2 14 13 15 Tightness OK o...

Page 4: ...xtra storage time Packaging The packaging material is to be disposed of in ac cordance with local regulations Disposal Components are to be disposed of separately in accordance with local regulations Certification Declaration of conformity We the manufacturer hereby declare that the prod uct GFK marked with product ID No 0063AU1408 complies with the essential requirements of the fol lowing Directi...

Reviews: