background image

Viridian VT2218

Instruction Sheet

102-483

SUPERSEDES: April 7, 2014

EFFECTIVE: May 12, 2014

Plant ID No. 001-4141

Delta-T Variable Speed, ECM High-Efficiency Circulator

DESCRIPTION:

The  Viridian  VT2218  circulator  is  a  temperature  sensing,  self-adjusting,  variable
speed  wet  rotor  circulator  with  an  ECM,  permanent  magnet  motor.  Operating
modes include Delta-T, constant speed, set point heat, set point cool, and boiler
protection.  Its  high  efficiency  motor  reduces  power  consumption  by  up  to  85%
compared to equivalent AC permanent split capacitor circulators.

APPLICATION:

• Maximum operating pressure: 125 psi (862 kPa)

• Maximum water temperature: 230°F (110ºC)

• Electrical specifications:

Voltage: 110-120V, 50/60 Hz, single phase
Maximum operating power: 58W
Maximum amp rating: 0.67

• Equipped with a cast iron casing and should be used for closed

loop systems only.

• Taco circulator pumps are for indoor use only – employer uniquement a

l’interieur.

• Acceptable for use with water or maximum of 50% water/glycol solution.

FEATURES:

• 5 operating modes:

- Delta-T; variable speed, maintains constant 

T, provides exact GPM flow required

- Constant Speed - 4 fixed speed options, maintains constant flow for zoning
- Set Point Heat - variable speed with boiler protection option, decreases speed on temperature rise
- Set Point Cool - variable speed, increases speed on temperature rise
- Boiler Protection - protects boiler from low return temperature and flue gas condensation

• Full LCD display showing:

- Mode, speed or temperature setting, watts, supply temperature, return temperature, and error

code diagnostics.

• Use with a Taco ZVC Zone Valve Control or SR Switching Relay for ON/OFF operation.

• Integral Flow Check (IFC) is included in carton. Simply press into discharge flange if required.

• Swivel-flanged casing provides 360° rotation mounting flexibility.

• BIO Barrier

TM

protects rotor and bearings from black iron oxide.

• Whisper quiet operation (<40dB)

INSTALLATION:

WARNING: Do not use in swimming pool or spa areas. Pump has not been investigated for these applications.
AVERTISSEMENT: Ne pas utiliser dans une piscine ou un spa. La pompe n'a pas été étudiée pour ces applications.

CAUTION: The addition of petroleum based fluids or certain chemical additives to systems using TACO equipment
voids the warranty. Consult factory for fluid compatibility.
ATTENTION:  L'ajout  de  liquides  à  base  de  pétrole  ou  de  certains  additifs  chimiques  à  des  systèmes  utilisant  un
équipement TACO annule la garantie. Consultez le fabricant pour connaître la compatibilité de liquides.

CAUTION:  Installations  at  elevations  over  5000  feet  must  have  higher  fill  pressure  of  20  psi  minimum  to  prevent
pump cavitation and flashing. Premature failure may result. Adjust expansion tank pressure to equal fill pressure. A
larger size expansion tank may be required.
ATTENTION: Des installations à des altitudes de plus de 1600 mètres doivent présenter une pression de remplissage
plus élevée de 20 psi au minimum afin d'éviter toute cavitation ou flashing de la pompe. Une défaillance prématurée
peut en résulter. Réglez la pression du réservoir d'expansion de façon qu'elle soit égale à la pression de remplis-
sage. Un réservoir d'expansion d'une taille supérieure peut être nécessaire.

Summary of Contents for Viridian Delta-T

Page 1: ...y temperature return temperature and error code diagnostics Use with a Taco ZVC Zone Valve Control or SR Switching Relay for ON OFF operation Integral Flow Check IFC is included in carton Simply press into discharge flange if required Swivel flanged casing provides 360 rotation mounting flexibility BIO BarrierTM protects rotor and bearings from black iron oxide Whisper quiet operation 40dB INSTALL...

Page 2: ...NE 2 V2 V2 V3 V3 P P ZONE 3 ZONE 3 V2 V3 P AIR PURGING SEQUENCE BY ZONE LAST FIRST KEY VI V2 V3 SHUT OFF ISOLATION VALVE P TACO CIRCULATOR WITH IFC FF FAST FILL BOILER FEED VALVE PV4 PURGE VALVE RECOMMENDED PURGING STEPS 1 CLOSE V1 PV4 V2 2 OPEN V3 3 OPEN FF VALVE 4 OPEN V2 PV4 TO PURGE LAST ZONE FIRST ZONE 3 5 CLOSE FF VALVE 6 CLOSE V2 PV4 7 REPEAT STEPS 1 TO 6 FOR EACH ADDITIONAL ZONE PURGE ZONE...

Page 3: ... M ZV1 ZV2 ZV3 M M M M M SUPPLY T SENSOR WIRING RETURN SUPPLY T SENSOR WIRING RETURN 3 KEY VI V2 V3 SHUT OFF ISOLATION VALVE P TACO CIRCULATOR WITHOUT IFC INSTALLED FF FAST FILL BOILER FEED VALVE PV4 PURGE VALVE ZV ZONE VALVE RECOMMENDED PURGING STEPS 1 CLOSE V1 PV4 V2 2 OPEN V3 AND ZV3 3 OPEN FF VALVE 4 OPEN V2 PV4 TO PURGE LAST ZONE FIRST ZONE 3 5 CLOSE FF VALVE 6 CLOSE V2 PV4 7 REPEAT STEPS 1 T...

Page 4: ...sion be sure to add vibration dampeners to piping when mounting circulator to wall or floor joists ATTENTION Pour réduire la possibilité de transmission de bruit veillez à ajouter des amortisseurs de vibration à la tuyauterie lors du montage du circulateur sur des chevêtres de mur ou de plancher WARNING Risk of electric shock To reduce the risk of electric shock be certain that it is connected onl...

Page 5: ...sulter The VT2218 has 5 Operating Modes Delta T Varies speed to maintain a fixed temperature differential factory pre set mode Constant Speed 4 fixed speeds see pump curves on previous page to select desired performance Set Point Heat Increases speed to increase temperature includes Boiler Protection option Set Point Cool Increases speed to lower temperature Boiler Protection Varies speed to maint...

Page 6: ...In Constant Speed mode the VT2218 will always start and run at the pre set Speed Level 1 through 4 Only watts will be dis played Temperature sensors are not active in this mode Set Point Heat Mode with Boiler Protection option 50 F 220 F default 105 F BP default 140 F In Set Point Heat mode the VT2218 will start at the lowest speed It then immediately switches to Variable Speed operation increasin...

Page 7: ...sor disconnected Reconnect sensor SENSOR 1 SHORTED Bad sensor Replace sensor SENSOR 2 SHORTED Bad sensor Replace sensor AC INPUT UNDER VOLTAGE Low voltage problem Check power supply AC INPUT OVER VOLTAGE High voltage problem Check power supply LOCKED ROTOR Probable locked rotor or motor failure Replace pump MOTOR OVER CURRENT Possible locked rotor Replace pump OVER TEMPERATURE PC Board overheating...

Page 8: ...to make changes in details of design construc tion or arrangement of materials of its products without notification TACO OFFERS THIS WARRANTY IN LIEU OF ALL OTHER EXPRESS WARRANTIES ANY WARRANTY IMPLIED BY LAW INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS IS IN EFFECT ONLY FOR THE DURA TION OF THE EXPRESS WARRANTY SET FORTH IN THE FIRST PARAGRAPH ABOVE THE ABOVE WARRANTIES ARE IN LIEU OF ALL ...