Positive pressure

(Rp ¼)

Atmospheric pressure

(Rp 

1

/

8

)

Connect

Seal

Free

Positive 
pressure 
DG..S

1

 4 

 If the electrical contacts in the DG..S could be 

soiled by dirt particles in the surrounding air or 
in the medium, use a filter pad at port 

4

.

Wiring

 

If the DG..SG has switched a voltage > 24 V 
and a current > 0.1 A once, the gold plating 
on the contacts will have been burnt through. It 
can then only be operated at this power rating 
or higher power rating.

 

Pressure switch DG can be used in Zone 1 
and 2 hazardous areas if an isolating ampli-
fier is installed upstream in the safe area as 

“Ex-i”  equipment pursuant to EN  60079-11 

(VDE 0170-7):2007.

 

DG as “simple electrical equipment” pursuant to 
EN 60079-11:2007 corresponds to the Tempera-
ture class T6, Group II. The internal inductance/
capacitance is Lo = 0.2 μH/Co = 8 pF.

 

In the case of low switching capacities, such as 
24 V, 8 mA, for example, we recommend using 
an RC module (22 Ω, 1 μF) in air containing 
silicone or oil.

 CAUTION

Please observe the following to ensure that the DG 
is not damaged during operation:

–  Note the switching capacity, see page 4 (Tech-

nical data).

 1 

  Disconnect the system from the electrical power 

supply.

M16 x 1,5:

ø 4,5–10 mm

3

4

2

5

6

7

M16 x 1,5:

ø 4,5–10 mm

3

4

2

5

6

7

 

Contacts 

3

 and 

2

 close when subject to increas-

ing pressure. Contacts 

1

 and 

3

 close when sub-

ject to falling pressure.

NO

2

NC

1

COM

3

L1

COM

3

NC

1

NO

2

Adjustment

 

The switching point is adjustable via hand wheel.

 1 

  Disconnect the system from the electrical power 

supply.

 2 

 Detach the housing cover, see page 3 (Wir-

ing).

 3 

 Connect an ohmmeter.

NO

2

NC

1

COM

3

COM

3

NC

1

NO

2

0

1 cm = 1 mbar

 4 

 Set the switching point using the hand wheel.

 5 

 Connect a pressure gauge.

NO

2

NC

1

COM

3

COM

3

NC

1

NO

2

0

1 cm = 1 mbar

 6 

  Apply pressure. In doing so, monitor the switch-

ing point on the ohmmeter and the pressure 
gauge.

Type

Adjusting range* 

[mbar]

Switching dif-

ferential** 

[mbar]

DG 6

0.4 – 6

0.2 – 0.3

DG 10

1 – 10

0.25 – 0.4

DG 30

2.5 – 30

0.35 – 0.9

DG 50

2.5 – 50

0.8 – 1.5

DG 150

30 – 150

3 – 5

DG 400

50 – 400

5 – 15

DG 500

100 – 500

8 – 17

*  Adjusting tolerance = ± 15% of the scale value.
**  Mean switching differential at min. and max. setting.

 

If the DG does not trip at the desired switch-
ing point, correct the adjusting range using the 
hand wheel. Relieve the pressure and repeat 
the process.

Summary of Contents for DG..S Series

Page 1: ... WARNING Indicates possible danger to life and limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Transport On receipt of the product check that the delivery is complete se...

Page 2: ...orrosion of the lower section pressure supply can become blocked and de formation of the diaphragm causing the switching point to shift Continuous operation at high temperatures accel erates the ageing of elastomer materials In places where a high thermal capacity is required thermal equipment trips must be installed upstream of the DG Use approved sealing material only Check max ambient temperatu...

Page 3: ...ed during operation Note the switching capacity see page 4 Tech nical data 1 Disconnect the system from the electrical power supply M16 x 1 5 ø 4 5 10 mm 3 4 2 5 6 7 M16 x 1 5 ø 4 5 10 mm 3 4 2 5 6 7 Contacts 3 and 2 close when subject to increas ing pressure Contacts 1 and 3 close when sub ject to falling pressure NO 2 NC 1 COM 3 L1 COM 3 NC 1 NO 2 Adjustment The switching point is adjustable via...

Page 4: ...entire system temporarily 15 minutes 2 bar Switching capacity DG U 24 250 V AC I 0 05 5 A at cos ϕ 1 I 0 05 1 A at cos ϕ 0 6 DG G U 5 250 V AC I 0 01 5 A at cos ϕ 1 I 0 01 1 A at cos ϕ 0 6 DG G U 5 48 V DC I 0 01 1 A Max medium temperature 15 to 80 C Storage and transport temperature 40 to 80 C RoHS compliant pursuant to 2002 95 EC Diaphragm pressure switch silicone free Diaphragm IIR Housing glas...

Reviews: