2
TECHNICAL DATA
10
OPTIWAVE 6300 C
www.krohne.com
04/2011 - 4000305604 - TD OPTIWAVE 6300 R04 en
Electrical connections
Power supply
Terminals output 1 - Non-Ex / Ex i:
Terminals output 1 - Non-Ex / Ex i:
Terminals output 1 - Non-Ex / Ex i:
Terminals output 1 - Non-Ex / Ex i:
14
…
30 VDC; min./max. value for an output of 22 mA at the terminal
Terminals output 1 - Ex d:
Terminals output 1 - Ex d:
Terminals output 1 - Ex d:
Terminals output 1 - Ex d:
20
…
36 VDC; min./max. value for an output of 22 mA at the terminal
Terminals output 2 - Non-Ex / Ex i / Ex d:
Terminals output 2 - Non-Ex / Ex i / Ex d:
Terminals output 2 - Non-Ex / Ex i / Ex d:
Terminals output 2 - Non-Ex / Ex i / Ex d:
10
…
30 VDC; min./max. value for an output of 22 mA at the terminal (additional
power supply needed - output only)
Cable entry
M20×1.5;
½
NPT
G
½
(not for FM- and CSA-approved devices. Not for stainless steel housings.)
M25×1.5 (for stainless steel housings only)
Cable gland
Standard: none
Options: M20×1.5 (for non-Ex and Ex -approved devices with M20×1.5 and M25×1.5
cable entries); others are available on request
Cable entry capacity (terminal)
0.5
…
1.5 mm
²
Input and output
Current output
Current output
Current output
Current output
Output signal
(Output 1)
4
…
20 mA HART
®
or 3.8
…
20.5 mA acc. to NAMUR NE 43
3
Output signal
(Output 2 - optional)
4
…
20 mA (no HART
®
signal) or 3.8
…
20.5 mA acc. to NAMUR NE 43
Resolution
±
3
µ
A
Temperature drift
Typically 25 ppm/K
Error signal
High: 22 mA; Low: 3.6 mA acc. to NAMUR NE 43
PROFIBUS PA
PROFIBUS PA
PROFIBUS PA
PROFIBUS PA
Type
4-wire (+ local HART) level transmitter; K-band FMCW radar
Function blocks
7 (level, distance, level conversion, level mass, reflection, ullage conversion and
distance mass)
Protocol / Communication
standard
PROFIBUS PA protocol that agrees with IEC 61158-2, galvanically isolated
Physical layer types
Standard power signaling, bus powered, non I.S.
Other features
Bus interface with integrated reverse polarity protection
Device power supply (24 V input)
18...30 VDC
Current consumption on
PROFIBUS network
20 mA
Output data
Level, distance, level conversion, level mass, reflection, ullage conversion or
distance mass
Input data
None
Error current FDE
Typically 0 mA (FDE =Fault Disconnection Electronic)
Address range
0...125. Default address: 126.
FOUNDATION Fieldbus
FOUNDATION Fieldbus
FOUNDATION Fieldbus
FOUNDATION Fieldbus
Type
4-wire (+ local HART) level transmitter; K-band FMCW radar
Function blocks
1 × Resource Block (RB), 4 × Analog Input Blocks (AI), 1 × Transducer Block (TB)
Analog Input Block: 50 ms
Protocol / Communication
standard
Foundation Fieldbus protocol that agrees with IEC 61158-2, galvanically isolated
ITK version
5.1