 COMMISSIONING / OPERATION 

18 

OPTIWAVE 5200 C

www.krohne.com

10/2013 - 4003066901 - MA OPTIWAVE5200C-PA-R01-en-

Bit Number

su

pported

Description

Cor

rective action

16

yes

Error appears

-

17

yes

Error disappears

-

24

1

Hardware failure electronics

Restart the device. If the error occurs again: send the device back 

to the manufacturer with an indication of the error.

27

1

Electronic temperature too low

Electronic temperature below -40

°

C. Comply with the application 

limits with regard to temperature of the medium and ambient 

temperature. If the process conditions are within the specified 

limits: send the device back to the manufacturer with an 

indication of the error.

Electronic temperature too high

Electronic temperature above +85

°

C. Comply with the application 

limits with regard to temperature of the medium and ambient 

temperature. If the process conditions are within the specified 

limits: send the device back to the manufacturer with an 

indication of the error.

28

1

Memory error

Reset the device to Factory/Default settings. If the error occurs 

again: send the device back to the manufacturer with an 

indication of the error.

29

1

Measurement failure

Check process conditions (Flow/Level, Temperature). If the 

process conditions are within the specified limits: send the device 

back to the manufacturer with an indication of the error.

34

1

Configuration invalid

Reset the device to Factory/Default settings. If the error occurs 

again: send the device back to the manufacturer with an 

indication of the error.

35

yes

Restart

Device is restarted because of power-up or warmstart request. In 

case of unexpected restart: send the device back to the 

manufacturer with an indication of the error.

36

yes

Coldstart

Device is reset to its Factory/Default settings because of a user 

request or exchange of the basic module (serial number is 

changed). Recover user specific parameter settings.

37

yes

Maintenance required

Linearization or temperature compensation is not operating 

correct. See for detailed failure message or send the device back 

to the manufacturer with an indication of the error.

39

yes

Ident_Number violation

Ident. Number Selector was modified while cyclic data transfer 

was active. To clear this message perform one of the following 

actions:

Reset Ident. Number Selector to its former setting

Stop cyclic data transfer

Restart the device

40

2

Maintenance alarm

Check detailed diagnosis. Restart the device. If the error occurs 

again: send the device back to the manufacturer with an 

indication of the error.

42

2

Function check

Simulation is active. Disable simulation to clear this message.

43

2

Invalid process condition

Check process conditions (Flow/Level, Temperature). If the 

process conditions are within the specified limits: send the device 

back to the manufacturer with an indication of the error.

55

yes

Extension available

Refer to detailed diagnosis in bits 56 to 103.

56

3

Converter EEPROM Error

Replace the signal converter. For more data, refer to the 

handbook.

57

3

Converter RAM Error

Replace the signal converter. For more data, refer to the 

handbook.

Summary of Contents for OPTIWAVE 5200 C

Page 1: ...OFIBUS PA interface The documentation is only complete when it is used in combination with the relevant documentation of the level meter OPTIWAVE 5200 C OPTIWAVE 5200 C OPTIWAVE 5200 C OPTIWAVE 5200 C...

Page 2: ...ry 4 2 2 Device description 4 2 3 Function blocks and the PROFIBUS PA Profile 4 2 4 Technical data 5 3 Electrical connection 6 3 1 Topology of a PROFIBUS PA network 6 3 2 Electrical connection for sig...

Page 3: ...the readme txt files 1 2 Scope of the document These instructions are supplementary to the standard product documentation of the signal converter The details described herein in particular the safety...

Page 4: ...PLC The control system cyclic communication services can read or write input and output data The device has these blocks Issued Signal converter Application program System integration Mth year Hardwa...

Page 5: ...rface This interface agrees with IEC 61158 2 bit rate 31 25 kbit s voltage mode MBP Manchester Coded Bus Powered Device power supply 9 32 V bus powered no additional power supply required Polarity sen...

Page 6: ...provides the conversion to the PROFIBUS DP bus line In addition it provides the power supply for bus powered PROFIBUS PA devices Refer to the instruction manual of the segment coupler concerning the D...

Page 7: ...ant that the system components and in particular the bus cables are shielded These shields must have as few gaps as possible Use the shortest possible length of shield wire to connect the electrical c...

Page 8: ...n address with the network bus ON The user can set the address of the device with the 7 other DIP swtiches item 2 You cannot use the network bus or the local display to change the station address 2 7...

Page 9: ...code 2712 reset station address to its default value are used If No_add_Cfg flag is set to ON the device will continue to use FACTORY_RESET code 2712 If the Station Address DIP switches are changed fr...

Page 10: ...download 4 3 Ident Number Manufacturer specific Ident Number 4554hex Manufacturer specific Ident Number 4554hex Manufacturer specific Ident Number 4554hex Manufacturer specific Ident Number 4554hex T...

Page 11: ...nt couplers If this file is used Condensed Status is not available 4 4 Configuration of cyclic data transfer During network configuration the user has to select which function block input output data...

Page 12: ...g slot 4 byte float value Float Format according to IEEE Standard 754 Short Real Number 1 byte status value Float value Float value Float value Float value The example that follows shows the format of...

Page 13: ...tus and Diagnosis automatically during start up of the cyclic data transfer by setting the parameter PRM_COND within the Set_Prm service data using an engineering tool e g DD DTM to write the paramete...

Page 14: ...verride value not usable Quality Quality substatus Limits Gr Gr QS QS QS QS Qu Qu 27 26 25 24 23 22 21 20 0 1 0 0 1 0 x x substitute set 0 1 0 0 1 1 1 1 initial value 0 1 1 0 1 0 x x maintenance deman...

Page 15: ...ad function block output value is bad do not use it for process control The Quality Substatus and Limit bits will be used for further diagnostics or limit checking Classic Status Classic Status Classi...

Page 16: ...s Gr Gr QS QS QS QS Qu Qu 27 26 25 24 23 22 21 20 0 1 0 0 0 0 non specific 0 1 0 0 0 1 last usable value 0 1 0 0 1 0 substitute set 0 1 0 0 1 1 initial value 0 1 0 1 0 0 sensor conversion not accurate...

Page 17: ...DD DTM to read it Cyclic services transfer diagnosis data to the control system PLC Diagnosis is bitwise coded Thus it is possible to report more than one indication simultaneously The GSD file conta...

Page 18: ...send the device back to the manufacturer with an indication of the error 35 yes Restart Device is restarted because of power up or warmstart request In case of unexpected restart send the device back...

Page 19: ...the device until the ambient temperature is back in the given range If the temperature does not stay in the correct range make sure that there is insulation around the signal converter If this error o...

Page 20: ...back in the given range If the temperature does not stay in the correct range make sure that there is insulation around the signal converter 93 3 Local Operation The device is in configuration mode A...

Page 21: ...NOTES 5 21 OPTIWAVE 5200 C www krohne com 10 2013 4003066901 MA OPTIWAVE5200C PA R01 en...

Page 22: ...5 NOTES 22 OPTIWAVE 5200 C www krohne com 10 2013 4003066901 MA OPTIWAVE5200C PA R01 en...

Page 23: ...NOTES 5 23 OPTIWAVE 5200 C www krohne com 10 2013 4003066901 MA OPTIWAVE5200C PA R01 en...

Page 24: ...products Products and systems for the oil gas industry Measuring systems for the marine industry Head Office KROHNE Messtechnik GmbH Ludwig Krohne Str 5 47058 Duisburg Germany Tel 49 0 203 301 0 Fax 4...

Reviews: