6
OPERATION
74
OPTISWIRL 2100
www.krohne.com
04/2020 - 4007600701 - MA OPTISWIRL 2100 R01 en
6.8 A12 plausibility checks
When configuring the device, a number of complex "cluster" checks are run internally on the
proposed configuration in order to make sure it is valid. Thus when saving a configuration the
device might raise an error like this: "Failed E01", which indicates an error cluster number.
In this case please consult the indicated cluster number in the following table to find out which
parameters are affected.
You may also want to enter in the quick setup menu "A12 Cluster Checks" and check each
setting in the affected "cluster" submenu.
No. Name
Explanation of plausibility checks
01
Sensor
Configuration /
Fluid
After changing fluid or operating density the device checks whether the measurement
variables configured at the device
’
s outputs are still valid (HART
®
variables, pulse output,
local display and flow totalizer). Also their configured ranges are checked.
02
03
Medium
When selecting the medium the device checks whether the measurement variables
configured at the device
’
s outputs are still valid (HART
®
variables, pulse output, local display
and flow totalizer).
05
Current output /
primary HART
variable
Checks if selected measurement variable is valid. Also checks limit settings for 0% and
100%.
06
Secondary HART
variable
Checks if the secondary HART
®
variable is valid.
Also checks if the selected measurement variable is available in this context and if its range
is valid.
07
Tertiary HART
variable
Checks if the tertiary HART
®
variable is valid.
08
Quaternary HART
Variable
Checks if the measurement variable configured as quaternary HART
®
variable is valid.
09
Flow Totalizer
Checks if the measurement variable selected for the flow totalizer (volume flow, standard
volume flow, mass flow) is valid. Also checks configuration of the HART
®
variables and local
display.
10
Measurement
Display Pages
Checks if the measurement variables are valid.
If a bar graph is displayed its ranges are also checked.
Table 6-32: A12 plausibility checks