INSTALLATION
2
7
MS15 - MS40 SERIES
www.krohne.com
06/2020 - 4007717401 - AD ATEX MS15-MS40 R01 en
2.1 Precautions
2.1.1 General notes
You can download the certificate from our website.
2.1.2 Special conditions
Make sure that:
•
you can get access to the device,
•
there is sufficient space around the device for inspections
•
you can see the device nameplate, and
•
there are no external forces applied on the device.
2.1.3 Electrostatic discharge
Do not install in a location where the electrostatic charge can increase. For example:
•
locations near ventilation systems,
•
locations where there is a risk of an increase in electrostatic charge caused by compressed
air and dust,
•
locations near machines that use friction,
•
locations near systems that apply electrons as a spray (e.g. near electrostatic painting
systems), and
•
locations near other machines and systems that can have large electrostatic charges.
WARNING!
When you install the device, obey the conditions in the EU-Type Examination certificate. These
conditions include:
•
The special conditions for safe use.
•
The Essential Health and Safety Requirements.
DANGER!
This installation must agree with EN 60079-14: Explosive atmospheres
–
Part 14: Electrical
installations design, selection and erection.
WARNING!
EPL Ga equipment - with an aluminium housing
EPL Ga equipment - with an aluminium housing
EPL Ga equipment - with an aluminium housing
EPL Ga equipment - with an aluminium housing
The aluminium housing of the device is a possible source of ignition in a potentially explosive
atmosphere.
Install the device in an applicable location to make sure that iron/steel objects do not hit or rub
against aluminium parts.
DANGER!
Risk of electrostatic discharge from the label and painted surfaces.