2.7 Electrical data
The connection may only be made using separately certified intrinsically safe isolating amplifiers
or zener barriers with the following maximum values per circuit:
Electrical values for ESK4... ...
The connector behind the cutout on the ESK4... module cover connects internal intrinsically safe
circuits. Only certified modules of type ESK4-I/O, ESK4-FF or ESK4-PA may be connected.
The additional connector on the ESK4-I/O module connects the optional display as an internal
intrinsically safe circuit.
Type of signal output
Terminals Maximum value per intrinsically safe circuit
U
i
I
i
P
i
C
i
L
i
ESK4...
11, 12
30 V
130 mA
1 W
0 nF
10
µ
H
ESK4-I/O
1, 2, 3 or
4, 5, 6 or
7, 8
30 V
130 mA
1 W
10 nF
0
µ
H
ESK4-FF / ESK4-PA
D, D-
24 V
380 mA
5.32W
0 nF
0
µ
H
FISCO FIELD DEVICE