Supplementary documentation BM 100 A with PROFIBUS-PA

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 

R

 D-47058 Duisburg

5/7

Tel.: 0203-301 309 

R

 Fax: 0203-301389 · e-mail: [email protected]

Units
Independent from the units within the local operating display Level and Distance values will be transmitted in „m“
always. Depending from the volume table Volume will be transmitted as cubic metres (m3) or tons (t).

 

1.3 Meaning of measurement and status information

Each configured measurement value is a 4 Byte Float Format according IEEE Standard 754 Short Real Number. A
status byte follows each measurement value. That means each measurement value consists of 4 byte value plus 1
byte status. Other measurement values will directly follow as 5 Byte package if configured.
First an example of the float format:

Float Format

Byte n

Byte n+1

Byte n+2

Byte n+3

Bit7

Bit6

Bit7

Bit6

Bit7

Bit7

VZ 2

7

2

6

2

5

2

4

2

3

2

2

2

1

2

0

2

-1

2

-2

2

-3

2

-4

2

-5

2

-6

2

-7

2

-8

2

-9

2

-10

2

-11

2

-12

2

-13

2

-14

2

-15

2

-16

2

-17

2

-18

2

-19

2

-20

2

-21

2

-22

2

-23

Exponent

Mantissa

Mantissa

Mantissa

Example:

40 F0 00 00 (hex) = 0100 0000 1111 0000 0000 0000 0000 0000 (binary)

Calculation:

Value

= (-1)

VZ 

* 2 

(Exponent - 127)

 * (1 + Mantissa)

Value

= (-1)

0   

* 2 

(129 - 127)

 * (1 + 2

-1

 + 2

-2

 + 2

-3

)

Value

= 1 * 4 * (1 + 0,5 + 0,25 + 0,125) = 7,5

Status (1 Byte)

Quality

Quality-Substatus

Limits

Gr

Gr

QS

QS

QS

QS

Qu

Qu

2

7

2

6

2

5

2

4

2

3

2

2

2

1

2

0

0

0

 

 

=  bad

0

1

  = uncertain

1

0

  = good (Non Cascade)

Status = bad
  0

  0

  0

  0

  0

  1

  = configuration error

  0

  0

  0

  0

  1

  1

  = device failure

  0

  0

  0

  1

  0

  0

  = sensor failure

  0

  0

  0

  1

  1

  1

  = out of service

Status = uncertain

0

1

  0

  0

  0

  1

  = last usable value

0

1

  0

  0

  1

  1

  = initial value (value before first measurement)

0

1

  0

  1

  1

  0

  = sub-normal (appears if level or interface level has been frozen)

Status = good

1

0

 

 

0

 

 

0

 

 

0

 

 

0

 

 

=  ok

1

0

1

0

0

1

 

 

=  maintenance  required

Status = Limits

 

 

0

 

 

0

 

 

=  ok

 

 

0

 

 

1

 

 

=  low  limited

  1

  0

  = high limited

  1

  1

  = constant

Check the first two quality bits in order to get the quality information of the measurement value:
Good (non Cascade)

measurement value is ok and can be used without restrictions

Uncertain

measurement value can be used but the accuracy can not be guaranteed (e.g. measurement
value has been frozen or A/D converter is saturated)

Bad

measurement value is bad don´t use it

The „Quality-Substatus“- and „Limit“-Bits can be used for further diagnostics or limit checking.

Attention:

The status should be watched always because a valid number will be transmitted even if the status of
the measurement is bad or uncertain. This is the only chance to check the meaning of the
transmitted measurement values.

Summary of Contents for BM 100 A

Page 1: ...NE 07 2000 KROHNE Messtechnik GmbH Co KG Ludwig Krohne Str 5 R D 47058 Duisburg 1 7 Tel 0203 301 309 R Fax 0203 301389 e mail krohne krohne de Supplementary Installation and Operating Instructions BM...

Page 2: ...LY 3 SOFTWARE HISTORY 3 1 PROFIBUS PA 3 1 1 PROFIBUS PA SERVICES 4 1 2 NETWORK CONFIGURATION 4 1 2 1 GSD file 4 1 2 2 Cyclic data exchange 4 1 3 MEANING OF MEASUREMENT AND STATUS INFORMATION 5 2 ELECT...

Page 3: ...and connection to a PROFIBUS PA fieldbus Attention Please set the controller to manual mode before changing parameters of the BM 100 A Items included with supply In addition to the standard scope of s...

Page 4: ...can be placed in the project This will then enable the cyclic communication measured values and status 1 2 2 Cyclic data exchange During network configuration the user has to define which measurement...

Page 5: ...Exponent 127 1 Mantissa Value 1 0 2 129 127 1 2 1 2 2 2 3 Value 1 4 1 0 5 0 25 0 125 7 5 Status 1 Byte Quality Quality Substatus Limits Gr Gr QS QS QS QS Qu Qu 27 26 25 24 23 22 21 20 0 0 bad 0 1 unce...

Page 6: ...4 1mH km C 80 200nF km the approved input values of the field devices Uo Io Po are matchable with the output values of the power supply e g segmment coupler which menas UI Uo II Io und PI Po 2 2 Bus...

Page 7: ...e not PROFIBUS PA The value must not be changed 1 6 2 ADDRESS Input 0 126 Settings out of the range will be ignored If out of range 126 will be used as default value Address can be changed via local d...

Reviews: